The effect of chlorination on the _plumbo-solvency_ of water was
investigated in 1904 by Houston who found that chlorine, as chloros, in
amounts between one and ten parts per million, did not appreciably
increase the plumbo-solvent action of either unfiltered or filtered
water. Similar results were obtained by the author with the Toronto
supply: raw lake water, filtered water, and water treated with 0.25 and
0.50 p.p.m. of chlorine, all dissolved the same quantity of lead in
twenty-four hours. The amount in each case was too small to be of any
significance.
BIBLIOGRAPHY
[1] Letton. J. Amer. Waterworks Assoc., 1915, 2, 688.
[2] Kienle. J. Amer. Waterworks Assoc., 1915, 2, 690.
[3] Adams. J. Amer. Pub. Health Assoc., 1916, 6, 867.
CHAPTER VI
BLEACH TREATMENT
The treatment of water with bleach alone has been largely supplanted by
the liquid chlorine process but the following details will be of use on
meeting conditions for which liquid chlorine cannot be used and also for
the preparation of the hypochlorite solution required in the chloramine
process.
The essential features of a bleach installation are the solution or
mixing tanks, storage tanks, piping system, discharge orifice or weir,
and sludge drain.
Bleach is usually sent out by the manufacturers in sheet steel drums, 39
inches high and 29-1/2 inches in diameter, which contain about 14 cu.
ft. of bleach and weigh approximately 750 pounds gross and 690 pounds
net. It can be most economically purchased in car lots and if the
consumption warrants this procedure storage should be provided for about
70 drums or rather more than one car load. According to Hooker[1] bleach
loses 1 per cent of available chlorine per month in hot seasons and 0.3
per cent in cold ones so that it is advisable to carry as little stock
as possible during hot weather. Hot weather also causes a further loss
by accelerating the action of the bleach on the drum which rapidly
disintegrates and cannot be handled. Bleach can often be purchased more
cheaply in hot weather but such a policy is a short sighted one unless
it is required for immediate use.
The general design of a hypochlorite plant is largely determined by the
capacity but in all cases an effort should be made to avoid complicated
details which may appear advantageous in the drafting office but do not
stand up in actual practice. Many metals rapidly develop a protective
coating on immersion in bleach solution but if this is removed by
friction, rapid erosion ensues; bearing metallic surfaces should be
reduced to a minimum.
_Mixing Tanks._ All tanks, whether mixing or storage, should be
constructed of concrete and painted with two coats of asphalt.
Experience has shown that wooden tanks are not suitable. The author has
used pine, oak, and cypress tanks but all were rapidly leached by the
hypochlorite and ultimately had to be lined with concrete.