EXAMPLE--With an unknown resistance connected between the posts 1 and 2,
the galvanometer showed a balance for a dial reading of 387. The number
opposite 387 in the table is .6313; hence, X = .6313 × 100 = 63.13 ohms.]
[Illustration: Fig. 590.--Diagram of the Queen standard potentiometer. The
circuit arrangement is a method of sub-dividing the main potentiometer
wire, MNOPQ, so as to provide for very accurate reading. The secondary
voltage, or that used to supply current to the main potentiometer circuit,
is adjusted by regulating rheostats, "Fast," "Medium," and "Slow" so that
the current flow is exactly .0001 ampere. It is noted that this instrument
requires a very small current for its operation. The instrument is
direct reading for voltage measurements, not exceeding 1.4+. In order to
determine if the current flow through the potentiometer be exactly .0001
ampere, the terminals of the standard cell binding posts are connected
in circuit so that the drop over points between which they are connected
are exactly equal to the voltage of the standard cell used. Binding posts
are provided for connection with various standard cells. The unknown
voltage to be measured is placed in opposition to the current flow in the
potentiometer circuit by connecting to the binding post "XEMF." Observe
that polarity is connected as required. The galvanometer with its shunt
is placed in the standard cell circuit, or X circuit, by means of a
double pole, double throw switch. The switch at T provides for standard
cells of different values and the setting at U allows for temperature
correction. The range of the instrument in volts can be increased by means
of multipliers or volt boxes.]
[Illustration: Fig. 591.]
[Illustration: Fig. 592.]
[Illustration: Fig. 593.]
[Illustration: Figs. 591 to 594.--Diagrams illustrating loop testing. To
properly understand the Murray or Varley loop tests, consider a Wheatstone
bridge (fig. 591) the arms of which are equal. In loop testing, the
rheostat is replaced by a length of cable and the unknown resistance also
by a length of cable, as in fig. 592, both being similar in resistance per
foot. If both lengths be the same, their resistances are the same and the
bridge balances. Now shorten one cable and add resistance in series with
it until the bridge again balances as in fig. 593. The added resistance
equals that of the piece cut off. Hence, if the resistance per foot be
known, the length of the shorter piece can be easily calculated. In the
Murray and Varley tests, the battery circuit is by ground connections
instead of by wire. In the Murray loop the arrangement is similar to fig.
592, the battery circuit being completed by ground connection through
fault in defective cable. Fig. 594 shows the general arrangement of the
Varley loop.]