If copper also is present (5) concentrate the filtrate from the lead
sulfate until the alcohol is expelled, and add an excess of ammonium
hydroxide. (6) Remove any iron precipitate by filtration. Neutralize the
filtrate (7) with sulfuric acid, and add 2 cc. of concentrated sulfuric
acid and 1 gram of urea. Electrolyze the solution and determine copper
colorimetrically as described in the procedure for copper (p. 54). After
the copper has been deposited add ammonium hydroxide to the solution
containing the zinc until nearly all the sulfuric acid has been
neutralized, concentrate to slightly less than the capacity of the
platinum dish, add 1.5 grams of potassium sulfate and 2 grams of
potassium oxalate, and electrolyze for zinc. As this solution is usually
saturated with ammonium salts due to neutralizing the large quantity of
sulfuric acid, it is frequently impossible to get the zinc deposited
firmly on the dish before the salts interfere by crystallization. To
avoid this difficulty, dilute half the solution and electrolyze it for
zinc; or, if the amount of zinc is very small, precipitate the zinc as
sulfide in acetic acid solution, wash, ignite to oxide, and weigh the
precipitate. This difficulty will not be encountered if copper is absent
as there will then be no excess of ammonium salts.
If lead and copper are known to be absent and zinc alone is to be
determined (13), after treating with sulfuric acid for separation of
lead, slightly dilute the contents of the dish. Add an excess of
ammonium hydroxide to precipitate iron and filter. Make the filtrate
slightly acid with sulfuric acid, concentrate to about 150 cc., transfer
to a weighed platinum dish, add potassium oxalate and sulfate, and
electrolyze the solution as described for deposition of zinc.
COPPER.[77]
Use 1 liter of a sample containing 0.1 to 1.0 part per million of
copper, and proportionate amounts for other concentrations. Evaporate to
about 75 cc., and wash into a 100 cc. platinum dish. Add 2 cc. of dilute
sulfuric acid for clear and soft waters; add more acid to very alkaline
waters to offset the alkalinity; add 5 cc. of acid to waters carrying
much organic matter or clay to insure the formation of a soluble copper
salt. Then place the dish as the anode in a direct current circuit,
suspend a spiral wire cathode in the solution so that it is parallel to
and about half an inch from the bottom of the dish, and close the
circuit.