(_b_) Apparatus not requiring pressure regulators must be so
arranged that the gas pressure cannot exceed sixty-tenths (6) inches
water column.
This requires the use of the pressure relief provided for in Rule No. 20
(_a_).
(_c_) Apparatus requiring pressure regulators must be so arranged
that the gas pressure cannot exceed three pounds to the square inch.
The pressure limit of 3 pounds is taken since that is the pressure
corresponding to a water column about 6 feet high, which is about, the
limit in point of convenience for water-sealed reliefs.
22. AIR MIXTURES.--Generators must be so arranged as to contain the
minimum amount of air when first started or recharged, and no device or
attachment facilitating or permitting mixture of air with the gas prior
to consumption, except at the burners, shall be allowed.
Owing to the explosive properties of acetylene mixed with air, machines
must be so designed that such mixtures are impossible.
23. PURIFIERS.--(_a_) Must be constructed of galvanised iron or
steel not less than No. 24 U.S. Standard gauge in thickness.
(_b_) Where installed, purifiers must conform to the general rules
for the construction of other acetylene apparatus and allow the free
passage of gas.
(_c_) Purifiers must contain no carbide for drying purposes.
(_d_) Purifiers must be located inside of gasholders, or, where
necessarily outside, must have no hand-holes which can be opened without
first shutting off the gas-supply.
24. PRESSURE REGULATORS.--(_a_) Must conform to the rules for the
construction of other acetylene apparatus so far as they apply and must
not be subject to sticking or clogging.
(_b_) Must be capable of maintaining a uniform pressure, not varying
more than four-tenths inch water column, at any load within their rating.
(_c_) Must be installed between valves in such a manner as to
facilitate inspection and repairs.
_Class B.--Stationary Apparatus for Central Station Service._
Generators of over 300 lights capacity for central station service are
not required to be automatic in operation. Generators of less than 300
lights capacity must be automatic in operation and must comply in every
respect with the requirements of Class A.
25. GENERAL RULES. GENERATORS.--(_a_) Must be substantially
constructed of iron or steel and be protected against depreciation by an
effective and durable preventive of corrosion.
Galvanising is strongly recommended as a protection against oxidation,
and it may to advantage be reinforced by a thorough coating of asphaltum
or similar material.
(_b_) Must contain no copper or alloy of copper in contact with
acetylene, excepting in valves.
(_c_) Must be so arranged that generation will take place without
overheating; temperatures in excess of 500° F. to be considered
excessive.
(_d_) Must be provided with means for automatic removal of
condensation from gas passages.
(_e_) Must be provided with suitable protection against freezing of
any water contained in the apparatus.