[Illustration: Fig. 691.--Diagram showing another and better method
of coupling compound dynamos in parallel. With this arrangement the
idle machines are completely disconnected from those at work. The same
reference letters are common in both diagrams. S, S' are switches; F,
F' fuses; A, A' ammeters, which indicate the total amount of current
generated by each of the machines; AC, AC', automatic switches, arranged
for automatically switching out a machine in the event of the pressure at
its terminals being reduced through any cause; R, R,' are hand regulators,
inserted in the shunt circuits of each of the machines, by means of which
the pressures of the individual machines may be varied and the load upon
each adjusted. The pressure at the bus bars is given by the voltmeter V,
one terminal of which is connected to each of the bars; a second voltmeter
may be used, to give the pressure of any individual machine, by connecting
"voltmeter keys" to the terminals of each of the machines, or a separate
voltmeter may be used for each individual machine. The only essential
difference between figs. 690 and 691 is, that in fig. 690 the equalizer
is connected direct to the positive brushes of all the dynamos, while
in fig. 691 the equalizer is brought up to the switchboard and arranged
between the two bus bars, a switch being fitted for disconnecting it from
the circuit when the machine to which it is connected is not working.]
Ques. How is a compound dynamo, running in parallel, cut out of circuit?
Ans. The load is first reduced to a few amperes, as in the case of shunt
dynamos, either by easing down the engine, or by cutting resistance into
the shunt circuit by means of the hand regulator, and then opening the
switch. Previous to this, however, it is advisable to increase the voltage
at the bus bars to a slight extent, as while slowing down the engine
the load upon the outgoing dynamo is transferred to the other dynamo
armatures, and the current in their series coils not being increased in
proportion, the voltage at the bus bars is consequently reduced somewhat.
Equalizing the Load.--When a number of compound dynamos of various output,
size, or make, are running together in parallel, it frequently happens
that all their characteristics are not exactly similar, and therefore the
load is unequally distributed, some being overloaded, while others do not
take up their proper share of the work.