Incorrect Adjustment of Regulators.--When shunt and compound machines
are provided with field regulators, it is possible that the resistance
in circuit may be too great to permit the necessary strength of exciting
current passing through the field windings. Accordingly, the fault is
corrected by cutting out more or less of the resistance. The field coils
of series machines are sometimes provided with short circuiting switches
or resistances arranged to shunt the current across the field coils. If
too much of the current be shunted across, the switch should be opened,
or if there be a regulator, it should be so adjusted that it will pass
enough current through the field windings to excite the machine.
Speed too Low.--In shunt and compound dynamos there is a certain critical
speed below which they will not excite. If the normal speed of the machine
be known, it can be seen whether the failure to excite arises from this
cause, by measuring the speed of the armature with a speed indicator. In
all cases it is advisable, if the machine do not excite in the course of a
few minutes, to slightly increase the speed. As soon as the voltage rises,
the speed may be reduced to its regular rate.
[Illustration: Fig. 692.--Method of testing for break by short circuiting
the terminals of the machine. If the external circuit test out apparently
all right, and there be no defective contacts in any part of the machine,
and all short circuiting switches, etc., be cut out of circuit, the
machine still refusing to excite, short circuiting the terminals of the
machine should be tried. This should be done very cautiously, especially
in case of a high tension machine. It is advisable to have, if possible,
only a portion of the load in circuit, and the short circuit should
be effected as shown in the figure. The short circuit may be made by
momentarily bridging across the two terminals of the machine with a single
piece of wire. As this, however, is liable to burn the terminals, a better
plan is to fix a short piece of scrap wire in one terminal, and then with
another piece of insulated wire make momentary contacts with the other
terminal and the short piece of wire. If the machine excite, it will be
at once evident by the arc which occurs between the two pieces of wire.
As the voltage of a series machine when induced to build in this manner
generally rises very rapidly, great care should be taken that the contact
is at first only momentary, merely a rubbing or scraping touch of the
wires. The contact may be prolonged if the machine do not excite at the
first contact. Compound wound machines can often be made to excite quickly
by short circuiting their terminals in this manner.]
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account