Magneto Test for Grounded Armatures.--A magneto test for grounded
armatures is not to be recommended, as armatures often possess sufficient
static capacity to cause a magneto to ring even though there be no leak.
This is due to the alternating current given by the magneto for when the
circuit has capacity it acts as a condenser and at each revolution of the
armature of the magneto a rush of current goes out and returns, charging
the surfaces of the conductor alternately in opposite directions, and
ringing the bell during the process.
[Illustration: Fig. 709.--Method of binding armature winding. Complete
appliances for handling armatures in making repairs are usually not
available with most street railway companies, since they are so seldom
required. When needed, therefore, some temporary contrivance must be
resorted to for help in the dilemma. Should an armature burn out, some
local concern that makes coils and rewinds armatures may be available to
do the work; again, it will be necessary to send to the manufacturers for
a man, as soon as coils can be made ready for the work. In no case should
any but an experienced man be given charge of this work. But if there be
any doubt as to whether the armature is really burnt out, let a competent
man be the judge. When a large armature needs repairing, a pair of chain
tongs can be used on some part of the shaft when putting in the coils,
and a block and tackle, as shown, can be used, when putting on the band
wires. Do not finish one band and then cut off the wire, but run it over
for the next, etc. Then solder and trim off the wires.]
Breaks in Armature Circuit.--A partial or complete break in the armature
circuit is always accompanied by heavy sparking at the commutator, but
not, as a rule, by an excessive heating of the armature or slipping of
the belt, and this enables the fault to be distinguished from a short
circuit. The faulty part can always be readily located by the "flat" which
it produces upon the surface of the commutator. The armature circuit being
open at the faulty part, heavy sparking results at every half revolution
as the brushes pass over it, and as a consequence the corresponding
segments become "pitted" or "flattened" with respect to the others; they
may easily be discovered on examination.
Breaks in the armature circuit may occur in either the commutator
or in the coils of the armature. To ascertain whether it be in the
latter, carefully examine the winding of the faulty coil.
The defect may be sought for more particularly at the commutator end
of the armature, as breaks in the wire are most frequent where the
connections are made with the commutator segments. If no break can
be discovered, try passing a heavy current through the faulty coil by
means of the brushes.
If a partial break exist with sufficient contact to pass a current,
the coil will be heated at that point and may be discovered by running
the fingers over the coil.