Ques. If, in rocking the brushes, a position cannot be found at which the
sparking disappears, what is the probable cause of the trouble?
Ans. The brushes may not be set with the proper pitch, that is they may
not be separated a correct distance, or the neutral plane may not be
situated in the true theoretical position upon the commutator through some
defect in the winding, etc.
In this last named case, the brushes may be strictly adjusted to their
theoretically correct positions before starting the machine; then,
when the machine is started and the load put on, violent sparking
occurs, which cannot be suppressed by shifting the rocker. If,
however, one set of brushes only be observed, it will generally be
found that, at a certain position, the sparking at the set of brushes
under observation ceases or is greatly reduced, while sparking still
occurs at the other set. When this position is found, the rocker
should be fixed by the clamping screw, and the brushes of the other
set at which sparking is still occurring adjusted by drawing them back
or pushing them forward in their holders until a position is found
at which the sparking ceases. Correct position of the brushes and
the suppression of sparking is a matter of importance, and any time
spent in carefully adjusting the brushes will be amply repaid by the
decreased attention and wear of the brushes and commutator.
[Illustration: Figs. 713 to 715.--Brushes making bad contact. A brush
making a bad contact, as only at the shaded portion of figs. 713 and 714,
will not allow the short circuited coil enough time to reverse, causing
sparking and heating. The latter will also result from bad contact on
account of the surface being too small for the current to be carried off.
This form of bad contact is worse than that shown in fig. 715, where the
area of contact surface only is lessened. If the brushes do not make good
contact, they should be ground down.]
Bad Condition of Brushes.--If the contact faces of the brushes be fused or
covered with carbonized oil, dirt, etc., there will be bad contact which
is accompanied by heating and sparking. Simple examination will generally
reveal whether this be the case. The remedy is to remove the brushes, one
at a time if the machine be running, clean, file if necessary, trim, and
readjust.
If the brushes be exceedingly dirty, or saturated with oil, it will be
necessary to clean them with turpentine, benzoline, or soda solution,
before replacing.
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account