[Illustration: Fig. 611.--Diagram showing connections of Leeds and
Northrup potentiometer. The coils in the series AD are each 5 ohms, and
between each two there is a brass block with a reamed hole. A pair of
flexible cords with taper plug terminals to fit these holes is furnished.
These coils can be measured with an ordinary Wheatstone bridge and thus
compared with each other to a high degree of accuracy, even if the bridge
be not accurate. For potentiometer work, the essential point is that
they should be like each other, not that they should be accurately any
particular value. In the same way the resistance of the extended wire
can be compared with the resistance of the coils in AD. Its resistance
should be 1.1 times the value of any coil between A and D. Outside
connection with the extended wire may be made by using the posts marked
BR and -BA. This adjustment for balancing an unknown electromotive force
is accomplished by the manipulation of the two contact points M and M'.
The coils AD are arranged in a circle, a revolving switch moving M. A
checking device enables the operator to set this switch without taking his
eye from the galvanometer. The resistance S is of such value that when
it shunts the wire OB, the total resistance between O and B is 1/10 of
the same unshunted. When the shunt is applied, provided the total current
remain the same, the drop between any two points on AB will be 1/10 of
its previous value. The total current will remain the same provided the
total resistance in the circuit remain the same. This is accomplished
by making the coil K such that it exactly compensates for the reduction
in resistance caused by plugging in the shunt coil S. The low scale is
applied by moving the plug from the position 1 to the position .1. With
this change the potentiometer reads from .16 volt down by indicated
steps of .000005 volt. The reading is very simple. For instance, if M
stand at 1.2 and M' at 1.35 revolutions, the reading is 1.2135 volts.
The resistances of the instrument are wound upon metal spools, and are
therefore able to dissipate a comparatively large amount of energy. This
allows the potentiometer to be used for pressure measurements up to 16
volts without the use of a volt box.]