Ans. The external circuit should be closed, otherwise a closed circuit
will not be formed through the field magnet winding and the machine will
not build up.
Ques. What is understood by the term "build up"?
Ans. In starting, the gradual voltage increase to maximum.
[Illustration: Fig. 675.--Connections for two compound wound dynamos to
run in parallel. The series fields of the machines are connected together
in parallel by means of wire leads or bus bars, which connect together
the brushes from which the series fields are taken. This is known as
the equalizer and is shown by the line running to the middle pole of the
dynamo switch. By tracing out the series circuits it will be seen that
current from the upper brush of either dynamo has two connections to its
bus bar. One of these leads through its own field, and the other, by means
of the equalizer bar, through the fields of the other dynamo. As long as
both machines are generating equally there is no difference of pressure
between the brushes of either, but should the voltage of one be lowered,
current from the other would flow through its fields and thereby raise
the voltage, and at the same time reduce its own until both are equal.
The equalizer may then be called upon to carry much current, but to have
the machines regulate closely it should be of low resistance. It may also
be run as shown by the dotted lines, but this will leave all the machines
alive when any one is generating. The ammeters should be connected as
shown. If they were on the other side they would come under the influence
of the equalizing current and would indicate wrong, either too high or
too low. The equalizer switch should be closed a little before the main
switches are closed.]
Ques. How should a shunt or compound machine be started?
Ans. All switches controlling the external circuits should be opened, as
the machine excites best when this is the case. If the machine be provided
with a rheostat or hand regulator and resistance coils, these latter
should all be cut out of circuit, or short circuited, until the machine
excites, when they can be gradually cut in as the voltage rises.
When the machine is giving the correct voltage, as indicated by the
voltmeter or pilot lamp, the machine may be switched into connection
with the external or working circuits.
Ques. In starting a shunt dynamo, should the main line switch be closed
before the machine is up to voltage or after?