Lead poisoning
In the case of tinning baths, Duckering[4] describes completely
successful results when from the top of the hood a shaft at least 24
inches in diameter was carried vertically upwards into the open air to
a height of 18 feet, and the top of the shaft fitted with a wind screen
in the form of a very large cone, having its lower edge below the upper
edge of the shaft, and its nearest point at least 8 inches from the top
of the shaft. Smoke produced in large quantity at any point 6 inches
outside the front of the hood was entirely drawn into it. As, however,
the inrush of air caused an eddy of the fumes at the upper edge of
the opening, the edges of the hood were turned inwards, so that the
operation of wiping was done in a sort of short tunnel. In general, it
may be said that the diameter of pipes leading from hoods to the outer
air (on the efficacy of the draught in which success depends) is much
too small. Frequently mere increase in size will convert an indifferent
draught into a good one. The height of the hood also--_i.e._, the
distance between its lower border and the point where it joints
the duct--is of importance. The shorter this distance is, the less
serviceable does it become for the removal of fume. Indeed, it may even
retain the fume which, were the hood not present, would rise to the
roof. Sometimes safety is increased by making the hood double, leaving
a space between the two sheets, and so concentrating the draught at
the centre and at the margin. With a fan, ducts of less diameter can
be used than when dependence is placed on heat alone. A duct carried
into a chimney-stack has the advantage of dispersing the fume at a safe
distance from the workroom.
The variableness of the draught produced by heat makes it unsuitable
for removal of dust, except such as arises from skimming. The
receptacle for the skimmings should always be kept inside the canopy of
the hood. We have, however, seen the dust given off in the heading of
yarn dyed with chromate of lead successfully carried away under hoods
connected up by branch ducts with the main chimney-stack.
[Illustration: FIG. 1.--DAVIDSON’S SIROCCO PROPELLER FAN.]