In usual service, with the normal rate, it is advisable to stop the
discharge at 1.90 volts per cell. If the discharge rate is considerably
less than normal, the voltage should not be allowed to fall as low
as 1.90 volts per cell, for the reason that with a very low rate of
discharge the voltage will not begin to fall off until the limit
of capacity is almost reached. The fall in specific gravity of the
electrolyte also serves as an indication of the amount taken out and is
in direct proportion to the ampere-hour discharge, thereby differing
from the drop in voltage, which varies irregularly for different rates
and degrees of discharge. For this reason, under ordinary conditions,
the fall in specific gravity is to be preferred in determining the
amount of discharge.
The actual amount of variation in the specific gravity of the
electrolyte between a condition of full charge and a complete discharge
is dependent upon the quantity of solution in the containing vessel
compared with the bulk of the plates. When cells are equipped with
the full number of plates, the range will be about 35 points (0.035
sp. gr.); for instance, if the maximum specific gravity reached on
the preceding overcharge is 1.209, the extreme limit beyond which the
discharge should not be carried is about 1.174. If the cells have less
than the full number of plates, this range in specific gravity is
proportionately reduced, except in the case of the “pilot cell,” which
should be equipped with a device for displacing the excess electrolyte.
The available capacity is temporarily reduced at low temperatures; with
a return to normal temperature the capacity is regained.
The battery should preferably be charged at the normal rate. It is
important that it should be sufficiently charged, but the charge
should not be repeatedly continued beyond that point. Both from the
standpoint of efficiency and life of the plates the best practice is
the method which embraces what may be called a regular charge, to be
given when the battery is from one-half to two-thirds discharged, and
an overcharge to be given weekly if it is necessary to charge daily, or
once every two weeks if the regular charge is not given so often.
The regular charge should be continued until the specific gravity
of the pilot cells has risen to within five points of the maximum,
as shown on the last previous overcharge. For example, if on the
previous overcharge the maximum is 1.210, then on the following regular
charges the current should be cut off when the specific gravity of
the pilot cell reaches 1.205. The pilot cell method of noting the end
of charge should not be used with a battery unless all the cells are
approximately in the same condition. With an old battery whose plates
are not uniform, readings should be taken on each cell to determine the
end of charge.