If the bridge is used at all, it should be placed in the testing room,
and the same leads employed for testing insulation should be used. The
resistance of these leads should first be determined by connecting
them together and measuring; this resistance is subtracted from each
resistance measured.
=VII. General.=—The key to success in cable testing is great care
in every detail. The cable now being furnished is all tested with
galvanometers having constants from 200,000 to 250,000 megohms. It has
all been accepted after most careful test. The chances are that it
is good when it arrives at the post, unless it has been mechanically
injured in transit, which should be ascertained by careful inspection
when delivered at the post.
Do not accept a single measurement if it shows low resistance, but
repeat until certain of results. The time between trials on the same
conductor should be as great as practicable. For example: Measurements
showing low resistance made in the morning should be repeated in the
afternoon; those made in the afternoon should be repeated the next day;
the conductor being connected to earth during the interval between
tests.
APPENDIX NO. 5.
CARE AND PRESERVATION OF SUBMARINE MINE MATÉRIEL.
Frequent inspections of all articles of submarine mine equipment
should be made, not only to check up the property, but also to
determine the condition of all matériel, and especially to see if it
has been affected by dampness. These inspections should be thorough
and detailed, as only in this manner can there be impressed on those
directly charged with the care of the property the importance of
ventilation, dryness, and the proper use of preservatives.
The generating set, storage battery, motor-generators, casemate
transformers, power panel, and operating boards will be installed in
the mining casemate, and such tools, appliances, and materials as may
be used when this apparatus is in commission will also be kept there.
The explosive will be kept in the magazines and tested and cared for in
the manner prescribed in Appendix No. 1.
The multiple and single conductor cable will be kept in the cable tanks
as described in Appendix No. 4.
All other articles of equipment will ordinarily be kept in the
storehouse, and a noncommissioned officer will be placed directly in
charge. It shall be his duty to keep the matériel in the best possible
condition, using such details from the submarine mine detachment from
time to time as may be necessary to assist him in this work. He shall
check up all articles taken from the storehouse during practice and
report at the end of the day’s work any shortage in tools or appliances
that he may discover.