The dew-point temperature at which the air enters the spray chamber
and the final temperature are kept constant by motor-operated valves
which supply the heating coils with the necessary heat in the form of
steam. The motors are controlled by thermostats, placed to measure the
temperature of the air as it enters the saturator and the finished air
as it enters the rooms. If these conditions are now kept constant, the
finished air will be constantly 50 per cent. saturated.
[Illustration: FIG. 176.--School building section showing a complete
air-conditioning plant.]
A plant of this character is illustrated in Fig. 176. The figure
shows the exterior of the casings which enclose the tempering coils
and saturator at _A_, the eliminator at _B_, and the heating coils at
_C_. This is another draw-through type of plant where a fan, enclosed
in _D_, draws the air through the conditioning apparatus and forces
it through the sheet-iron ducts _E_. The passages in the walls--as
indicated by the arrows--conduct the air through the register _R_, into
the room. The register _S_ represents the discharge duct through which
the vitiated air is forced from the room.
In this system of air conditioning, all of the ventilating air is to
be saturated with moisture at a temperature such that when raised to
room temperature will contain the desired percentage of humidity. The
saturator occupies the space between _A_ and _B_. A number of spray
jets are arranged to fill the entire space with water drops that are
moving in every direction. The air, as it passes, must come into
contact with the drops again and again, until by repeated impact each
particle is completely saturated and at the same time washed free from
dust. It has already been explained that the movement of the saturated
air through a mass of spray will carry with it a considerable amount
of unabsorbed water that must be taken out by an eliminator. A section
of the casing is broken out at _B_, showing the eliminator plates. The
irregular surfaces of these plates repeatedly change the direction of
the passing air, and the suspended water or remaining solid matter is
thrown against the surfaces where they adhere. The moisture accumulates
in drops of water that run down the plates to the bottom of the
enclosure and finally into the sewer.
From the eliminator the air passes through the heating coils enclosed
in _C_, where it is heated to the necessary temperature for admission
to the rooms.
The regulation of the temperature of the tempering coils and heating
coils is accomplished as in the other plants described. The thermostats
with their motors operate the valves of the heaters to admit steam
sufficient to keep constant temperatures at the different parts. The
humidity is maintained at a constant amount by saturating the air at a
constant temperature and therefore no humidostat is required.