Pyrometry: A Practical Treatise on the Measurement of High TemperaturesDarling, Charles R. (Charles Robert)
Science
Pyrometry: A Practical Treatise on the Measurement of High Temperatures
Darling, Charles R. (Charles Robert)
Pyrometry
=Installations of Thermo-electric Pyrometers.=—When a number of
furnaces in the same establishment are to be controlled, considerable
economy may be effected by making one indicator serve for all the
couples, which in this case must necessarily be made up of wires
identical in thermo-electric value. Such an arrangement is shown in
fig. 27, in which H^1 and H^2 represent two couples, one wire from
each being connected to one of the terminals of the galvanometer G.
The other terminal of the galvanometer is connected to the arm D of
a switch, and the remaining thermocouple leads are connected to the
points 1 and 2 respectively on the circumference. As shown, H^1 is
connected to the galvanometer, and by turning the arm D to the point
2 the other couple would then be connected. Any number of junctions
may thus be arranged with a single indicator. When this arrangement
is adopted in a workshop, it is advisable to construct a small wooden
building at a spot convenient for most of the furnaces, in which the
indicator and switchboard are kept, and which could also contain a
recorder if necessary; a spot as free as possible from vibration being
preferable. Separate indicators are only necessary when a furnace is
used for special work.
[Illustration: FIG. 27.—CONNECTIONS FOR AN INSTALLATION OF
PYROMETERS.]
In some instances a second indicator is kept in the shop office, to
which all the pyrometers are wired, and which serves as a standard.
The scale of the office indicator is checked daily at one point;
and by connecting a given couple first with the shop indicator, and
immediately afterwards with the office standard, any errors can be
detected. It is also possible to ascertain the temperature of any given
furnace in the office at any time, and so to control the whole. In
fixing up such an arrangement it is necessary that each couple and its
leads, up to the indicator, should possess the same resistance, or
should not differ by an amount sufficient to affect the readings. The
general experience of a properly managed installation is that the cost
is saved in a few months in fuel alone; and, in addition, the work is
carried out to much better advantage owing to complete control from the
office.