=Control of Furnace Temperatures.=—Many attempts have been made
to secure the automatic regulation of furnace temperatures by means of
mechanisms controlled by an indicator or recorder. In the arrangement
employed by the Brown Company of Philadelphia, movable stops are
provided, which may be brought to any part of the scale, the mark
between the stops representing the temperature it is desired to
maintain. The indicator (or recorder) is provided with a presser-bar
which descends periodically; and if the temperature be too low the
depressed pointer completes a circuit through the inner stop, whilst
if too high the circuit is through the outer stop. Both circuits
contain a relay which brings a mechanism into operation, the result
being to increase the supply of electricity or gas if the temperature
be too low, or to diminish the supply when too high. When correct,
the depression of the pointer fails to complete either circuit, and
in this manner control between small limits may be ensured. In the
case of large furnaces the relay circuits are employed to light lamps
of different colours, the adjustment then being made by the man in
charge of the furnace. Arrangements of this kind effect a considerable
saving in fuel by preventing unnecessary heating, and are particularly
valuable in cases where overheating would be deleterious to the
articles in the furnace. The future will probably witness considerable
developments along these lines.
=Contact-Pen Recorders.=—The force with which the pointer of an
indicator is urged over the scale is relatively small, particularly in
the case of pyrometers in which the platinum series of metals are used,
as these furnish only a low E.M.F. If, therefore, the pointer terminate
in a pen which is in continuous contact with the record-paper, the
friction thus occasioned interferes considerably with the free movement
of the pointer. When cheap-metal pyrometers are used, which yield a
much higher E.M.F., the use of the pointer as contact-pen becomes
more feasible, and if uniform friction at all parts of the paper can
be ensured, records may be taken in this manner; and a recorder so
constructed is simpler and cheaper than those of the intermittent
type. Contact-pen recorders are used in America to some extent, being
made by Bristol, Brown, and others; but so far British makers have not
developed the manufacture of these instruments. At present, contact-pen
recorders must be considered less accurate and reliable than those in
which the contact is intermittent.