Records of Steam Boiler ExplosionsMarten, Edward Bindon
History
Records of Steam Boiler Explosions
Marten, Edward Bindon
Steam-boiler explosions
Small internally fired Boiler, 5ft. high, 2ft. 4in. diameter, and was
intended to work at 70 lbs. The fittings were defective, the spiral
spring of the safety valve being most easily altered, so as to cause
over pressure. The manhole was not strengthened by any ring, and the
first rents commenced at that point.
The cause of the explosion was over pressure and defective construction.
The sketch at No. 57 explosion in this year, is of a similar boiler
which exploded from nearly similar causes.
_No. 24. Bilston. (Fig. 14.) May 13th. none injured._
Balloon or Haystack Boiler, about 16ft. diameter, 5/16 inch plates, and
worked at very little above atmospheric pressure.
The boiler was chiefly used to store water during the time another
boiler by the side of it was emptied. When the water was required to
refill the other boiler, a fire was lighted under the balloon, and
sufficient steam generated to drive the water from it into the other
boiler. The safety valve never being used, it had become fast, and as
a little more steam than usual had accumulated, the bottom gave way,
and the reaction of the issuing contents made the boiler rise from its
seat, and it fell on its side at some distance away flattened by the
fall.
[Illustration: _Fig. 14._]
_No. 25. Westbromwich. (Fig. 15.) May 25th. none injured._
[Illustration: _Fig. 15._]
One Tube Cornish Boiler, 15ft. long, and 4ft. 6in. diameter, taper
tube, 2ft. 9in. diameter in front, and 2ft. diameter at back, 3/8 inch
plates, 40 lbs. The boiler rested on two walls forming the bottom flue.
There was a safety valve, a glass water gauge, a pressure gauge, and
two fusible plugs upon the tube.
Two longitudinal rents took place on the under side of the shell,
allowing two strips, forming the central part, to open out by the
continuation of the fracture, until they were blown to a considerable
distance. The tube with the front end, and one ring of the shell were
thrown to the front, while the back end was thrown to the rear, the
smallest end of the tube having torn away from the back.
The shell was deeply corroded where it rested on the side walls of
the bottom flue, and the strength of the boiler was thereby so much
reduced, that it was unable to bear the ordinary working pressure.
_No. 26. Halifax. (Fig. 16.)_ _May 26th. 1 killed._
[Illustration: _Fig. 16._]
One Tube Cornish, 24ft. 6in. long, and 5ft. diameter, taper tube,
slightly oval in the front, 2ft. 8in. diameter, and 2ft. diameter at
the back, 3/8 inch plates. The boiler was fitted with glass water
gauge, float, self-acting feed apparatus, and safety valve loaded to 52
lbs., and also a mercury gauge.
The tube collapsed over the fire, a rent taking place in the second
ring of plates. The issuing steam and water caused the death of a man
in front, but the shell of the boiler was not injured or moved.