Records of Steam Boiler ExplosionsMarten, Edward Bindon
History
Records of Steam Boiler Explosions
Marten, Edward Bindon
Steam-boiler explosions
One of three. One tube Cornish, with two external fire grates with a
water tube over each fire. It was 30ft. 2in. long, 6ft. diameter. Tube
3ft. diameter, 3/8 inch plates, 40 lbs. pressure. External shell is
shown in dotted lines to allow of the tubes being seen. The tube had
formerly been placed rather higher in the boiler. The tube collapsed
sideways, having become overheated from shortness of water. The boiler
itself was but little disturbed.
_No. 7. Kelso. (Fig. 6.) February 11th. none injured._
[Illustration: _Fig. 6._]
One tube Cornish, 9ft. 9in. long, 4ft. 6in. diameter. Tube 2ft. 3in.
diameter, 5/16 inch plates, 30 lbs. pressure. The boiler rent open at
the bottom, and was thrown a considerable distance by the reaction
of the issuing contents. The plates along the bottom were reduced by
corrosion to 1/16 inch where in contact with the brickwork, so that the
boiler was unable to bear the usual working pressure.
_No. 8. Durham. (Fig. 7.) February 12th. 2 killed, 1 injured._
[Illustration: _Fig. 7._]
One of four. External shell is shown in dotted lines in sketch, to
allow the tubes to be seen. It was 20ft. long, 7ft. diameter, 40 lbs.
pressure. The two internal fire grates in the flues were 2ft. 8in.
diameter, which joined at the back with a central return flue to a
chimney passing out of the top of the boiler. The sides of flues were
flattened to allow them to be packed closer together, and especially
the central return flue, which was flattened on both sides, and thus
rendered so weak that the left side collapsed and allowed the contents
of the boiler to issue, blowing out the grate on the left side.
_No. 9. Halifax. (Fig. 8.) March 3rd. none injured._
[Illustration: _Fig. 8._]
Plain Cylinder, with flat ends, 18ft. 6in. long, 3ft. 11in. diameter,
3/8 inch plates, 50 lbs. pressure. The back end gave way at the root
of the angle iron all round, and was thrown 60 yards to the rear. The
boiler was forced forward, and tilted up by the reaction of the issuing
contents, and forced through a wall. The cause of explosion was the
want of sufficient stays to the flat end.
_No. 10. Newcastle. (Fig. 9.) April 4th. 1 killed, 4 injured._
[Illustration: _Fig. 9._]
One of four. Plain Cylinder, 28ft. long, 6ft. diameter, 3/8 inch
plates, 30 lbs. pressure. The boiler was much torn and scattered,
and much damage was done. The plates were improperly arranged
longitudinally. The boiler gave way at a patch lately put on, and had
become so deteriorated by nearly 30 years' wear, that it was unable to
bear the usual pressure.
_No. 11. Aberdeen. April 7th. 1 killed._
Two tube Cornish, 6ft. diameter. Few particulars have been obtained.
The upper part of front end was blown out and did considerable damage.
Most likely this was for want of proper stays.
_No. 12. April 15th. 1 injured._