=79. Setting of Centrifugal Pumps.=—In setting a centrifugal pump, care
should be taken to provide a firm foundation to hold the shafts of the
pump and the electric motor or the reduction gearing in good alignment,
or to prevent the pump from being displaced by the pull of a belt. It is
desirable that the foundation be level. Centrifugal pumps should be set
submerged for small pumping stations automatically controlled. Sludge
pumps must be set submerged as otherwise they will not prime
successfully. Provision should be made by which the pump can be lifted
from the sewage, or sludge, for inspection and repair. In many cases the
pump can be made self-priming by setting it in a dry, water-tight vault
below the low level of sewage flow. Where possible it is desirable not
to set the pump submerged as it will receive better care when easily
accessible.
[Illustration:
FIG. 61.—Centrifugal Pump in Manhole at Duluth, Minn.
Eng. Contracting, Vol. 43, 1915, p. 310.
]
The suction pipe should be free from vertical bends where air might
collect and should be straight for at least 18 to 24 inches from the
pump casing. An elbow on the suction pipe, attached directly to the
casing of the pump gives a lower efficiency than a suction pipe with a
short straight run. Centrifugal pumps will operate with as high a
suction lift as reciprocating pumps, but at the start they must be
primed and some provision must be made for priming them. The suction
pipe should be equipped with foot valves to hold the priming, or some
method may be provided for exhausting the air from the suction pipe. The
foot valves should be so installed as to form no appreciable obstruction
to the flow of water. They should have an area of opening at least 50
per cent greater than the cross-section of the suction pipe. A strainer
on the suction pipe is undesirable as it becomes clogged and is usually
in an inaccessible position for cleaning. A screen should be placed at
the entrance to the suction well to prevent the entrance of objects that
are likely to clog the pump. A gate-valve and a check-valve should be
provided on the discharge pipe, the former to assist in controlling the
rate of discharge and the latter to prevent back flow into the pump when
it is not operating.
Centrifugal pumps are well adapted to service in either large or small
units. An installation in a manhole at Park Point, Duluth, is shown in
Fig. 61. This station is controlled by an automatic electric device
which is operated by a float in the suction pit. Such automatic control
is an added advantage of the use of electrically driven centrifugal
pumps. The Calumet Pumping Station in Chicago, shown in Fig. 49, has a
capacity of approximately 1,000 cubic feet per second. The simplicity of
the layout of this station is shown in Fig. 62.
[Illustration:
FIG. 62.—Interior Arrangement of the Calumet Sewage Pumping Station,
Chicago.
Eng. News-Record, Vol. 85, 1920, p. 872.
]
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account