Sewerage and Sewage TreatmentBabbitt, Harold E. (Harold Eaton)
History
Sewerage and Sewage Treatment
Babbitt, Harold E. (Harold Eaton)
Sewage disposal; Sewerage
The ordinary method of combating quicksand and in conducting work in wet
trenches is to drive water-tight sheeting 2 or 3 feet below the bottom
of the trench, and to dewater the sand by pumping. When dry it can be
excavated relatively easily. A more primitive but equally successful
method is to throw straw, brickbats, ashes, or other filling material
into the trench in order to hold the excavation once made, or this may
supplement the attempts at pumping, or the wet sand may be bailed out in
buckets. Successful excavation in quicksand requires experience,
resourcefulness. and a careful watch for unexpected developments. The
well points described in Art. 142 are used for dewatering quicksand.
=136. Pumping and Drainage.=—Ground water is to be expected in nearly
all sewer construction and provision should be made for its care. Where
geological conditions are well known or where previous excavations have
been made and it is known that no ground water exists it may be safe to
make no provision for encountering ground water. Where ground water is
to be expected the amount must remain uncertain within certain rather
wide limits until actually encountered.
In order to avoid the necessity for pumping, or working in wet trenches
it is sometimes possible to build the sewer from the low end upwards and
to drain the trench into the new sewer. The wettest trenches are the
most difficult to drain in this manner as the material is usually soft
and the water so laden with sediment as to threaten the clogging of the
sewer. It is undesirable to run water through the pipes until the cement
in the joints has set. This necessitates damming up the trench for a
period which may be so long as to flood the trench or delay the progress
of the work. If it is not possible to drain the trench through the sewer
already constructed the amount of water to be pumped can be reduced by
the use of tight sheeting.
[Illustration:
FIG. 95. Improvised Trench Pump.
]
Pumps for dewatering trenches must be proof against injury by sand, mud,
and other solids in the water. For this purpose pumps with wide passages
and without valves or packed joints are desirable. The types of pumps
used are: simple flap valve pumps improvised on the job, diaphragm
pumps, jet pumps, steam vacuum pumps, centrifugal pumps, and
reciprocating pumps. All are of the simplest of their type and little
attention is paid to the economy of operation because of the temporary
nature of their service.
=137. Trench Pump.=—A simple pump which can be improvised on the job is
shown in section in Fig. 95. Its capacity is about 20 gallons per minute
but its operation is backaching work. It is inexpensive, quickly put
together and may be a help in an emergency. It is to be noted that the
passages are large and straight, that there are no packed joints, and
that the velocity of flow is so small that it is not liable to clogging
by picking up small objects.
[Illustration:
FIG. 96.—Diaphragm Pump