All experience with this class of fuel indicates that the best results
are secured with high combustion rates. With a natural draft in the
furnace of, say, three-tenths inch of water, a combustion rate of from
250 to 300 pounds per square foot of grate surface per hour may be
obtained. With a blast of, say, five-tenths inch of water, this rate can
be increased to 450 pounds per square foot of grate surface per hour.
These rates apply to bagasse as fired containing approximately 50 per
cent of moisture. It would appear that the most economical results are
secured with a combustion rate of approximately 300 pounds per square
foot per hour which, as stated, may be obtained with natural draft.
Where a natural draft is available sufficient to give such a rate, it is
in general to be preferred to a blast.
Fig. 27 shows a typical bagasse furnace with which very satisfactory
results have been obtained. The design of this furnace may be altered to
suit the boilers to which it is connected. It may be changed slightly in
its proportions and in certain instances in its position relative to the
boiler. The furnace as shown is essentially a bagasse furnace and may be
modified somewhat to accommodate auxiliary fuel.
The fuel is ignited in a pit A on a hearth which is ordinarily
elliptical in shape. Air for combustion is admitted through the tuyeres
B connected to an annular space C through which the amount of air is
controlled. Above the pit the furnace widens out to form a combustion
space D which has a cylindrical or spherical roof with its top
ordinarily from 11 to 13 feet above the floor. The gases pass from this
space horizontally to a second combustion chamber E from which they are
led through arches F to the boiler. The arrangement of such arches is
modified to suit the boiler or boilers with which the furnace is
operated. A furnace of such design embodies the essential features of
ample combustion space and long gas travel.
The fuel should be fed to the furnace through an opening in the roof
above the pit by some mechanical means which will insure a constant fuel
feed and at the same time prevent the inrush of cold air into the
furnace.
This class of fuel deposits a considerable quantity of dust, which if
not removed promptly will fuse into a hard glass-like clinker. Ample
provision should be made for the removal of such dust from the furnace,
the gas ducts and the boiler setting, and these should be thoroughly
cleaned once in 24 hours.
Table 45 gives the results of several tests on Babcock & Wilcox boilers
using fuel of this character.
TABLE 45