Hollow-tile wall and concrete and stone have factors about the same as
for the furred brick wall.
[Illustration: SIDE ELEVATION]
4. Add to this the number of B. T. U.’s lost per
hour through the windows. This is determined by
multiplying the area of the windows by the heat
loss in B. T. U.’s per hour for each square foot of
window, which is 78.8 for single windows, and where
storm-windows are added it is 31.5 B. T. U.’s.
5. This total sum is the number of B. T. U.’s lost
through walls and windows for each hour.
6. To this must be added the heat lost by leakage
through the window-cracks. This is secured by
measuring the length of window-cracks on the
side which has the greatest length of crack and
multiplying this by 168, or the number of B. T. U.’s
lost each hour for each linear foot of window-crack.
For very tight windows reduce above to 84.
7. The total of all the above gives the number of
B. T. U.’s lost each hour from the room when the
outside temperature is zero and the inside is 70
degrees Fahrenheit.
Knowing the quantity of heat lost per hour, a radiator must be
installed which will supply this amount per hour. As the average
steam-radiator supplies about 250 B. T. U.’s per hour from each square
foot of its surface, the number of square feet required for a radiator
to be installed in the room can be found by dividing 250 into the
number of B. T. U.’s which were found to be lost from the room each
hour.
A hot-water radiator gives off about 150 B. T. U.’s per hour for
each square foot of surface, so that the radiator is generally about
one-third larger than the steam-radiator.
Knowing the required number of feet of radiation for the radiator, the
proper size can be selected from the manufacturer’s catalogue.
By lumping the total number of square feet of radiation for all the
radiators throughout the house together and adding 35 per cent to this
to make up for loss through pipes and under-rating of boilers, the size
of the boiler can be selected from the catalogue to fit this need.
To estimate the size of a warm-air furnace, the total quantity of heat
lost from all the rooms of the house should be calculated in the same
way, and then 25 per cent added to allow for cold attics and exposure.
This quantity should then be multiplied by 2.4 and divided by 8,000
to find the number of pounds of coal which will be required to be
burned per hour. By dividing this amount by 5, the grate area of the
required furnace can be found, and the correct size selected from the
manufacturer’s catalogue.
X LIGHTING AND ELECTRIC WORK
_Modern Developments_
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account