The comparisons between standards and waters are best made in bottles
of perfectly clear glass, holding at least a gallon, and the comparison
is facilitated by surrounding the bottles with black cloth except at
the point of observation, and lighting the water by electric lights so
arranged that the light passes through the water but is hidden from
the observer. In case the water under examination is colored, the
comparison is rendered difficult, and it is often advisable to add a
small amount of methyl orange to the standards to make the colors equal.
Instead of diluting a water of known turbidity for the standards, a
standard can be made by precipitating a known amount of silver chloride
in the water. For this purpose about one per cent of common salt is
dissolved in clear water and small measured amounts of silver nitrate
added, until the turbidity produced is equal to that of the water under
examination. The relation of the amount of silver nitrate used to the
turbidity is entirely arbitrary, and is established by comparisons of
standards made in this way with waters having turbidities from 0.02 to
0.04, the turbidities of which are measured with the platinum wire, and
which afterwards serve to rate the standards. The silver chloride has a
slight color, which is an objection to its use, and perhaps some other
substance could be substituted for it with advantage. The standards
have to be made freshly each day.
One disadvantage of the platinum-wire method of observing turbidities
in the open air, as compared with the diaphanometric method using
artificial light, is that observations cannot be made in the night. To
get the general character of the water in a stream, daily observations
taken about noon will generally be sufficient; but for some purposes it
is important to know the turbidity at different hours of the day, and
in such cases the platinum-wire method is at a distinct disadvantage.
Variations in the amount of light, within reasonable limits, do not
affect the results materially, although extreme variations are to be
avoided. The size of the wire also influences the results somewhat. The
wire commonly used is 0.04 of an inch or one millimeter in diameter.
A wire only four tenths of this size in some experiments at Pittsburg
gave results 25 per cent higher; with a wire twice as large the
results were lower, but the differences were much less. Wire 0.04 of
an inch in diameter was adopted as being very well adapted to rather
turbid river-waters. For very clear lake or reservoir waters, usually
transparent to a great depth, a much larger object is preferable.
Within certain limits the results obtained with an object of any size
can be converted into corresponding figures for another object, or
another light, by the use of a constant factor. Thus the turbidities
obtained with a platinum wire always have approximately the same ratio
to the turbidities of the same waters determined by the diaphanometer.
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account