be supplied depends upon the number of persons, and not on the cubic
space; but in exceptional instances, where the amount of cubic space
is very large in proportion to the number of persons, and the heating
is effected by warm air, it may require more air to keep the room at a
comfortable temperature than is necessary for the supply of the
occupants. The cubic space is also relatively much more important in
rooms which are to be occupied but a short time continuously, and can
then be thoroughly aired, than it is in rooms constantly occupied.
The methods of calculation can be best illustrated by one or two
examples. What should be the number and size of flues and registers
for fresh-air supply for a hospital ward to contain 24 beds, the ward
being a rectangular pavilion with windows on opposite sides? In this
case the room is constantly occupied, and the supply of air should be
1 cubic foot per head per second, or, in all, 24 cubic feet per
second. The velocity of current at the registers should not exceed 3
feet per second--better only 2. This will require from 8 to 12 square
feet of clear opening in the registers. If we allow four on each side
of the room, each register must have at least 1 square foot of clear
opening. The velocity of the air in the flues supplying these
registers should not exceed 4 feet per second, and therefore the area
of each flue should be about 9 by 12 {180} inches. Suppose the same
question be asked with regard to a school-room to contain 48 pupils.
In this case the room will not be occupied more than two hours at a
time. The air-supply desirable may be put down at 35 cubic feet per
head per minute, or 28 cubic feet per second for the whole. The
velocity in the flues may be put, as before, at 4 feet per second;
hence we need 7 square feet area of flue, or seven flues, each having
1 square foot of area. It is safe to say that there are not twenty
school-houses in the United States which have fresh-air flues of
sufficient area; the deficiency is made up, for the most part, by
leakage of the outer air through cracks around windows and directly
through the wall, and also by the passage of air from the central hall
into the room, this last air coming from the cellar or basement.
The velocity of the air at the foul-air registers and in the foul-air
ducts may be greater than in the fresh-air flues, since there is no
danger of its causing draughts, and hence there is no truth in the
common notion that the outlets should be larger than the inlets to
allow for the expansion of heated air. It is important that the
velocity of the current in the outlet shaft or chimney should be at
least 8 feet per second at the point where it escapes into the outer
air; and if the outlets be too large for the inlets, the result may be
that some of the foul-air flues will work backward and become inlets.
The plan of making everything a little larger than is necessary is not
a safe one as regards chimney-flues and outlet shafts.