Keeping this standard in view, the physician may be called on for an
opinion as to whether the ventilation of a given building is
satisfactory or as to the merits of a proposed plan for ventilation.
The first is a question of fact: What are the effects produced upon
the inmates? Are there unpleasant odors in the building or not? What
percentage of carbonic impurity is present? What is the number of
cubic feet of air per head that is introduced and removed per hour?
And what is the character of the fresh-air supply as to purity? Does
it come from the cellar, or from other rooms, or from a foul area?
Air-currents can usually be best investigated by the fumes of nascent
muriate of ammonia produced by {179} exposing a cylinder of common
blotting-paper, moistened with dilute hydrochloric acid, to the vapors
coming from a crumpled fragment of the same paper moistened with
common aqua ammonia and placed within the cylinder. The process for
carbonic acid determination is simple, and can be learned in three
hours in a laboratory under a skilful teacher. It does not seem worth
while to describe it here. The determination of the amount of air
passing through a given register, flue, or chimney in a given time is
to be made by the use of an anemometer, an instrument which registers
the velocity of the current of air passing through it.
In judging of the merits of a plan of ventilation the following points
should be remembered: The defect in most plans for ventilation is in
the air-supply. Many people suppose that they have made all necessary
provision for ventilation if they have put in tubes or openings for
the escape of foul air, forgetting that these outlets will have no
effect if corresponding inlets are not provided. Examine, first of
all, therefore, the ducts, flues, and openings proposed for the
fresh-air supply, with reference to their size and position and the
amount of air to be furnished by them. These will almost invariably be
found to be too small. The proper size of flues and registers for a
given room is ascertained by dividing the number of cubic feet of air
to be supplied per second by the velocity in feet per second which the
air is to have in the flue or opening, bearing in mind that it is much
better that these flues and registers shall be too large than too
small, since it is easy to reduce their capacity, but, in most cases,
impossible to increase it. When the fresh-air register is so situated
that the current of air from it is liable to strike upon the person of
an occupant of the room, the velocity of this current should not
exceed 1-1/2 feet per second if unpleasant draughts are to be avoided;
and it will usually be found best that the velocity of the air in the
flue shall not exceed 6 feet per second, except in the case of very
large flues, where the element of friction becomes of comparatively
small importance. In the great majority of cases the amount of air to
Public-domain text, read in full here on John Shaqi.