throughout the district by means of five sub-stations; and from this
board there branches a double system of mains, which run everywhere
side by side, one-half the mains being connected to the first machine
and one-half to the second, so forming an excellent arrangement for
the prevention of total extinction of the light. The mains running to
the sub-stations are on the divided system, which is introduced for
the purpose of saving copper, as in a solid cable the loss of pressure
is greatest when the full number of lamps is on, and decreases as the
lamps are extinguished. With the divided main system it is intended to
follow out Sir William Thomson’s formula, which equates the value of
the loss of head, and the interest on the saving on the copper. If for
a certain main this formula shows that a fall of 20 per cent. is the
most economical condition for working, then, since by the divided main
the pressure can be kept within a variation of 2 per cent. at the
distant end, it follows that a considerable saving can be effected over
an ordinary solid main. Special arrangements are adopted at Paddington
to keep the pressure constant, a fall of potential being allowed for;
thus at the engine-house the pressure is 150 volts, in the passenger
station it is 120 volts, and at Westbourne Park it is 100 volts. The
arc lamps are fed by the same mains, and are arranged two in series.
A small installation at Kensington Court, erected two years ago, for
the purpose of supplying the houses in the immediate neighbourhood,
has rapidly developed, and underground mains have been led in many
directions from the station, and a constant service of electricity
is provided for by means of secondary batteries. As this is the
first practical exposition of the secondary batteries’ system of
distribution, it is proposed to describe the installation under that
head. Central-stations are also at work in Liverpool, Leamington,
Taunton, Exeter, and there are also five large installations nearly
completed in London, besides the Kensington Court station, all of which
will probably be in full swing before the end of the year.
ELECTRIC LIGHTING from CENTRAL-STATIONS is now practically carried out
on five different methods.
I. BY SECONDARY GENERATORS OR TRANSFORMERS, WITH ALTERNATING
CURRENT.
II. THE EDISON OR PARALLEL SYSTEM, WITH CONTINUOUS CURRENT.
III. THE SERIES OR BERNSTEIN SYSTEM.
IV. MULTIPLE SERIES.
V. DISTRIBUTION WITH SECONDARY BATTERIES OR ACCUMULATORS.
CLASS I.
SUPPLY BY SECONDARY GENERATORS OR TRANSFORMERS.