If a pipe must be carried through a wood partition, protection for the
woodwork can be provided by cutting an opening in the partition and
inserting a galvanized-iron double-wall ventilating shield at least 12
inches larger than the pipe (fig. 13) or by using at least 4 inches of
brickwork or other incombustible material. Smoke pipes should never pass
through floors, closets, or concealed spaces or enter a chimney in a
garret.
Gases formed by burning the sulfur contained in coal are the main cause
of corrosion of metal smoke pipes. Little corrosion occurs during the
heating season, when the pipe is kept hot and dry.
The life of metal pipes can be prolonged if each summer when they are not
in use they are taken down, cleaned, wrapped in paper, and stored in a
dry place. This is especially true of pipe to heaters in damp cellars.
[Illustration: Figure 13.--_A_, Elevation of protection around a
stovepipe passing through a frame partition; _B_, sectional view.]
[Illustration: Figure 14.--Method of insulating wood floor joists and
baseboard at a chimney with 4-inch walls. A single header is used as it
is less than 4 feet long.]
_Insulation_
No wood should be in contact with a chimney. Leave a space of 2 inches
between the outside face of a chimney and all wooden beams or joists
except when 8 inches of masonry is used outside flue lining, in which
case the framing may be within one-half inch of the chimney masonry.
The space between the floor framing and the chimney may be filled with
porous, nonmetallic, incombustible material, such as loose cinders.
Brickwork, mortar, and concrete are not suitable. Place the filling
before the floor is laid, as it not only forms a fire stop but prevents
accumulation of shavings or other combustible material. Subflooring may
be laid within one-half inch of the masonry. Baseboards, when fastened to
plaster that is directly in contact with the wall of a chimney, can be
protected by a layer of fireproof material, such as asbestos, at least
one-eighth of an inch thick between the woodwork and the plaster (fig.
14).
Wooden studding, furring, or lathing should not be placed against a
chimney but set back, as indicated in figure 9; or the plaster may be
applied directly to the masonry or to metal lath laid over the masonry.
The former is the better method, as settlement will not crack the
plaster. It is recommended that a coat of cement plaster be applied
directly upon the outside surfaces of masonry chimneys that are to be
incased by a wooden partition or other combustible construction. Metal
lath, lapped 6 inches on the masonry, at the intersection of chimneys
with partitions prevents corner cracks. (See plan in fig. 34.)
_Chimney and Roof Connection_
Where the chimney passes through the roof, provide a 2-inch clearance
between the wood framing and masonry for fire protection and for
expansion due to temperature changes, settlement, or slight movement of
the chimney during heavy winds.