Building -- Estimates; Factories -- Design and construction; Hardware
The best possible design, therefore, for a fire-tower is that indicated
in Fig. 3. This construction is known as the =vestibule fire-tower=,
and from the plan it is seen that this combines safety and utility
in a small amount of space. The opening marked _a_ in the plan is
always open to the weather, and the floor of the vestibule is usually
concreted and graded to a drain that connects with the rain conductor
of the roof at _b_. By this arrangement, a well-protected line of
travel is obtained between the stairway and the buildings on each
floor, the occupants of the building being protected by the parapet
wall and iron railing, as indicated at _c c_. To this vestibule from
the factory a tin-lined, or fireproof, door must be provided, so
that after the people have left one floor it can be cut off from the
vestibule.
In the construction of all fire-towers, their walls must be carried by
means of parapet walls at least 3 feet above the roof of the building,
and the roof over them must be constructed of fireproof material.
When it is required, fireproof windows may be used in the walls of
brick-enclosed fire-towers. These windows may be constructed of sheet
metal and glazed with wire glass. If it is not possible to use such
windows, a skylight may be built over the top of the tower, but this
skylight must be constructed of sheet metal, or other non-combustible
material, and glazed with wire glass.
=10. Number of Fire-Towers.=—The number of tower fire-escapes required
for factory buildings of either the first, second, or third class,
may be established according to the number of stories in height of
the building, and the floor area, in square feet, for each floor;
that is, for buildings of the first class, three or four stories in
height, having one tower, the floor area of any floor may be as much
as 20,000 square feet, while if the height of the building of the same
construction is made twelve stories, the floor area should only be
6,500 square feet.
Where two tower fire-escapes are incorporated in the plan, a building
three or four stories in height may contain as many as 25,000 square
feet in the area of one floor, but if the building were increased to
twelve stories, the floor area of each floor should not exceed 15,000
square feet.
In buildings of the second and third classes, a greater number of tower
fire-escapes should be provided, and it is good practice to supply one
tower fire-escape in a three-story building of these classes for a
floor area not exceeding 10,000 square feet, or two tower fire-escapes
should the floor area not exceed 15,000 square feet. In buildings of
this construction, of from four to six stories in height, the floor
area should not exceed, for one tower fire-escape, from 6,000 to
3,500 square feet of floor area in each floor, while with two tower
fire-escapes the maximum floor area is from 12,000 to 8,000 square feet.