=37. Strength of Reinforced-Concrete Columns.=—In proportioning
reinforced-concrete columns, it is customary among conservative
engineers to figure the safe strength of the concrete-column section
at 500 pounds per square inch of section; that is, if the column is 20
inches square, its area is 400 square inches, and its safe strength at
500 pounds per square inch will be 200,000 pounds. In the top floor, it
is seldom advisable to use concrete columns less than 10 inches square,
though at this dimension they generally possess several times the
requisite amount of resistance.
All columns in reinforced construction generally have embedded in them
3¾-inch to 1-inch round steel rods, tied together with round iron
binders, or bar iron straps as indicated in Fig. 16 (_b_).
=38. Floor and Roof Construction.=—In considering the floor and roof
construction of buildings built of reinforced concrete, it will be
noted from Fig. 16 that the roof slab is made 3 inches in thickness.
Such a slab made of good concrete, reinforced with ⅜-inch steel rods,
spaced 6 inches from center to center, will carry the usual roof loads
for spans up to 7 feet in the clear.
In forming the gutter for such roofs, as indicated at _b_, the gusset
is made by filling in with cinder concrete. Usually cast-iron eave
boxes are embedded in the concrete, and these in turn connected with
inside rain conductors.
The beams supporting the roof, when the span is from 12 to 14 feet, are
made about 12 inches deep and 8 inches wide, while the girders, also
constructed of reinforced concrete, are usually made about 3 inches
deeper and 11 inches in width.
In order to make the roof impervious to moisture, a covering of felt
and slag is commonly employed. This slag joins the parapet wall with
the usual tin flashing and counter flashing, as at _c_, though copper
is recommended for best work.
In the floor construction of reinforced-concrete factory buildings,
the slabs forming the floor panels are made not less than 4 inches
in thickness, and seldom over 5 inches, with a 1-inch finish coat of
cement besides, if this character of finish is desired. Such a floor
slab is shown in the construction at _d_, Fig. 16, while the wooden
floor construction is shown in Fig. 16 (_c_). Here the structural
feature of the floor is a 4-inch concrete slab upon the top of which
is placed 2" × 3" beveled hemlock sleepers, the space between these
sleepers being filled with cinder concrete, and the floor finish
obtained by laying 1-inch tongued-and-grooved maple floorings.