Building -- Estimates; Factories -- Design and construction; Hardware
in which _w_ = weight of stack, in pounds;
_h_ = height of stack, in feet;
_d_ = mean diameter of stack, in feet;
_c_ = constant;
_b_ = width of base.
The constant _c_ varies with the shape of the stack. For a square
stack, when the wind is blowing at hurricane violence, 56 is used; for
an octagonal stack, 35; and for a round stack, 28.
To demonstrate this formula, consider a square chimney having an
average breadth of 8 feet and a width at base of 10 feet, the stack
being 100 feet high. The problem is, therefore, to find what the weight
of the stack must be in order to resist the greatest wind pressure
likely to occur. By substitution, in the formula,
100 × 100 × 8 × 56
_w_ = ------------------ = 448,000 pounds
10
With brickwork weighing about 120 pounds per cubic foot, the chimney in
question must therefore have an average thickness of somewhat more than
13 inches.
[Illustration: FIG. 32]
=66.= A good rule to follow in designing brick stacks is to make
the base at least one-tenth of the height. For stacks under 5 feet
in diameter, the walls for the first 25 feet from the top may be 8
inches, increased 4½ inches for each additional 25 feet from the top.
If the stack is more than 5 feet in diameter, the thickness at the top
should be 1½ bricks, or 12 inches, with a 4½-inch increase for each
25 feet. If the stack is less than 3 feet in diameter, the brickwork
for the first 10 feet from the top may be as little as 4½ inches; this
thickness, however, is not recommended, as the weather is likely to
penetrate such a thin wall, and sooner or later, together with the
exposure to the gases, destroy the brickwork.
=67. Construction of Brick Chimneys.=—All brick stacks must be provided
with a cast-iron or stone coping at the top, and it is usually well
to tie them in toward the base with good heavy stone band courses.
In constructing brick stacks, the brickwork should be laid up in
lime-and-cement mortar, and the bricks well covered and slid in place,
not just tapped or hit with the handle of a trowel.
All chimneys should also be provided, for a distance of at least
one-third of their height from the base, with a fire-brick lining, laid
up in fireclay, and at the bottom of this lining, where the flues from
the boiler enter the stack, cast-iron cleaning doors and frame should
be provided for removing soot that will accumulate and drop down. A
good example of a brick stack is given in Fig. 32; this stack has a
capacity of 500 horsepower, and is sufficiently stable to resist any
wind pressure.
FIRE-PROTECTION OF MILL BUILDINGS
SPRINKLER SYSTEM
Public-domain text, read in full here on John Shaqi.
Reviews
Reviews
No reviews yet
Be the first to share your thoughts on this work.
Elsewhere in the archive
Join the Discussion
Join the discussion
Sign in to leave a comment or review.
Sign InorCreate an account