[Illustration: Figs. 603 and 604.--Special loop test as made with the
Leeds and Northrup fault finder. Diagram showing connections for the
second measurement. The special loop test may be used to advantage where
the length of the cable or faulty wire only is known, and where there are
two other wires which may be used to complete the loop. To use an outside
battery, connect one pole to Ba, and ground the other. The pressure of
this battery must never exceed 110 volts; if it be over 25 volts, see that
switch W is open.]
The Potentiometer.--For the rapid and accurate measurement of voltage,
current, and resistance, the potentiometer can be recommended. Those in
charge of electric light and power companies, and also those who purchase
large amounts of electrical energy are realizing, more and more, the
necessity of having satisfactory primary standards with which to check
their volt-, ampere-, and watt-meters.
When it is realized that an error of one per cent. in a commercial
instrument means an error of one dollar one way or the other in every
one hundred dollars charged, the need of such standardization apparatus
becomes at once apparent.
The potentiometer, it should be noted, relies for its accuracy, only upon
the constancy and accuracy of resistances and upon standard cells.
With the materials now available, and the skill which has been acquired
in their manufacture, both the resistances and the standard cells are
obtainable which are remarkably constant, and both can be readily checked
for accuracy.
Location of Opens.--These measurements are based on the fact that the
capacity of wires in a cable is ordinarily a measurable quantity, which,
in wire of uniform diameter, is proportionate to length. In making these
tests, a fault finder is used together with a buzzer, dry cells to operate
it, small induction coil, and telephone receiver. These instruments are
to be found in any telephone exchange. It is best to locate the buzzer at
some distance from the fault finder in order that it cannot be heard by
the operator.
[Illustration: Fig. 605.--To use galvanometer of Leeds and Northrup fault
finder in series with the battery: Set switches as shown, and connect
between posts Gr. and 2 (see figs. 587 and 588). The galvanometer will
have the maximum sensibility with the pointer at 1,000 and the minimum at
zero.]