[Illustration: Fig. 606.--To measure high resistances, such as the
resistances of faults with Leeds and Northrup fault finder. _First
Method._--Arrange the switches as shown in the figure. Connect posts Gr.
and 2, turn the handle until the galvanometer needle comes to rest at
an even deflection of ten divisions. Call the reading A. Connect in the
unknown resistance between Gr. and 2. Now close the switch W, so that the
figure 1 appears on the top of the block, and again bring the galvanometer
to a deflection of ten divisions and call the reading B. Then X = (10,000
B ÷ A) - 1,000. In case X be a high resistance, it will be found that
the galvanometer will not deflect ten divisions for any position of the
pointer. In such case, choose a number of divisions which is a factor of
ten, such as 5, 2, or 1, and multiply (10,000 B ÷ A) by ten divided by
the number chosen, as 10/5, 10/2, 10/1. For example, for a deflection
of two divisions: X = (10/2)(10,000 B ÷ A) - 1,000. The satisfactory
range of the set for high resistance measurement may be increased by
using an outside battery of higher voltage. With the contained battery,
satisfactory measurements can be made up to 1 or 2 megohms. When outside
battery is used, connect one terminal to the post Ba, and the other to 2
for the reading A. Connect the battery and unknown resistance in series
between these posts for the reading B. When an outside pressure of 25
volts or over is used, the switch W should not be closed unless there be
a resistance in series with the battery of 10,000 ohms or over. _Second
Method._--For use as a voltmeter to measure high resistances. (More
convenient but not quite as accurate as first method.) Set the switches to
RV, M and 10. Turn the knurled nut on the galvanometer so as to set the
needle to the extreme right hand side of the scale. Connect the posts 2
and Gr. with a short piece of wire. Turn the rotating pointer on the scale
until the galvanometer needle moves over about 20 scale divisions when
the battery key is closed. Remove the connection between 2 and Gr. as the
voltmeter terminals. This makes a simple way of testing for various kinds
and amounts of trouble. On a wet cable a deflection of 10 to 15 divisions
indicates heavy enough trouble to locate with the fault finder. With a
little care, trouble showing only 5 or 6 divisions can be located.]
Before attempting locations for opens it is well to make the following
measurements:
1. The insulation of the broken wire and the insulation of the good wire
with which it is to be compared.
This may be done as shown in fig. 606. It is best that the insulation
resistance be fairly good, but experiments indicate that good results
can be obtained by the methods which follow, even when the insulation
is as low as 100,000 ohms, and fair results when as low as 50,000 to
100,000 ohms.