[Illustration: Fig. 607.--Diagram of connections in testing for opens with
Leeds and Northrup fault finder. The apparatus required consists of fault
finder, buzzer, dry cell to operate buzzer, small induction coil, and
telephone receiver. Connect the battery to the primary of the induction
coil, one terminal of the secondary to the post Ba, and the other to the
connected wires as shown. Set switches U and V so as to short circuit the
two resistance coils.]
2. The resistance between the two sections of the broken wire should be
measured.
This may be done by joining the broken wire and a good wire at the
distant end of the cable and measuring the resistance of the loop. To
ensure close locations, this resistance should be over 100,000 ohms.
Fair locations can be made when the resistance is much lower and it is
worth while to attempt it even if the resistance be as low as 10,000
ohms. The difficulty of determining the balance point increases as
the resistance decreases.
Ques. Describe the method of locating an open with a fault finder.
Ans. (_Case I_) The broken wire will be one of a pair. Select another pair
in the cable that will have the same capacity per mile and join together
the mate of the broken wire and one wire of the other pair. Make the
connections as shown in fig. 607, then depress the battery key and move
the contact to the point of minimum sound in the telephone. The distance
to the break is equal to LA ÷ (1,000 - A), where L is the length of the
good wire.
EXAMPLE: A cable 1.45 miles long contained a broken wire. It was found
that the insulation resistance of the end of this wire was over 10
megohms, as was that of the good pair selected to test against it. The
resistance between the two pieces of the good wire was also over 10
megohms. Connections were made as in fig. 607, and it was found that
the balance point was 476. Accordingly from the table
A / (1,000 - A) = 0.9084
and
d = 1.45 × .9084 = 1.317 + miles.
[Illustration: Fig. 608.--Diagram of connections in testing with Leeds
and Northrup fault finder for open wire in telegraph and other cables
in which the wires are not grouped in pairs. Connect the broken wire to
1. Select a good wire and join to 2. Connect all other wires and ground
them, by connecting to the cable sheath. Connect the distant end of the
broken wire to the others. Ground the end of the induction coil that is
not connected to the post Ba.]
Location of Opens.--(_Case II_) Open wire in telegraph or other cables in
which the wires are not grouped in pairs. The connections are made as in
fig. 608, and the measurement and calculation exactly as in the preceding
case.