The double circuit breaker is an ordinary single-coil breaker. The
single circuit breaker is an overload and reverse-current circuit
breaker. The reverse-current coil has two windings, one of which is
bridged across the power supply, and the other is in series with it. On
charge, the effect of these coils is differential, and on discharge it
is cumulative and will trip the circuit breaker when the current from
the storage battery exceeds 2 amperes.
[Illustration: FIG. 3.—OPERATING BOARD.]
To charge the storage battery:
(_a_) From an external source of power: Both the single
and the double circuit breakers are closed and switch No. 2
is closed to the right (facing the board).
(_b_) From the casemate generator: Both circuit
breakers are closed and switch No. 2 is closed to the left
(facing the board).
=The operating board.=—A front view of this is given in figure 3, its
wiring diagram in figure 18 at the end of the book. One is required
for each group of 19 mines. It consists of an iron frame to which are
attached a signal block, a master block, 19 mine blocks (1 for each
mine), busses, and a terminal bar with 19 numbered terminals. The frame
is 78 inches high by 24 inches wide. It should be set up so that its
face is 34 inches from the wall in rear.
=The signal block= (see fig. 18).—This is an enameled slate block 24
inches wide and 11 inches high, upon which are mounted three binding
posts, three lamps (red, white, and green), a bell and bell switch, a
90-ohm non-inductive resistance in parallel with the white lamp, and
a 125-ohm resistance in series with the bell. The binding posts are
marked “Earth” or “G.,” “A. C.,” and “D. C.,” respectively. The bell,
the 90-ohm non-inductive resistance, and the 125-ohm resistance are so
indicated on the figure. The lamps are marked as follows: Red, “R. L.”;
white, “W. L.”; green, “G. L.”
The circuit, under normal conditions, is: From negative D. C. bus on
power panel, to switch 3 closed up, to “operating board” terminal, to
D. C. lead, to D. C. post on signal block, through green lamp, to D.
C. jaw on master block, to D. C. bus on operating board, through power
switch P on mine block, through solenoid S, to middle of testing switch
T, to upper contact of same, to upper contact of automatic switch A, to
middle of same, to mine switch M, through same to terminal bar, through
19-conductor and single-conductor cables, through mine transformer
primary, to mine case, to ground, to D. C. “earth” terminal on power
panel, to switch 3, and to positive D. C. bus on power panel.