Practical Methods of Sewage Disposal for Residences, Hotels and InstitutionsOgden, Henry N. (Henry Neely)
Science
Practical Methods of Sewage Disposal for Residences, Hotels and Institutions
Ogden, Henry N. (Henry Neely)
Sewage disposal
150│ 3│ 2000│ 8 × 8 │ 6│ 20
175│ 3│ 2330│ 8 × 9 │ 6│ 20
200│ 5│ 1600│ 8 × 12 │ 8│ 20
250│ 5│ 2000│ 10.5 × 12 │ 8│ 20
300│ 5│ 2400│ 12 × 13 │ 8│ 20
350│ 5│ 2800│ 13 × 14 │ 8│ 20
400│ 5│ 3200│ 13 × 17 │ 8│ 20
450│ 5│ 3600│ 13 × 19 │ 8│ 20
500│ 5│ 4000│ 13 × 21 │ 8│ 20
─────────┴─────────┴─────────┴────────────┴─────────┴─────────
The siphons in each instance should be so placed that the lower edge of
the bell of the siphon will be at a distance below the roof of the tank
equal to twelve inches plus the drawing depth or discharging depth of a
siphon of the diameter indicated. There should be three inches of space
between the siphon bell and the floor of the chamber. The discharging
depths of siphons as used in forming Tables 2, 3, 4, and 5 are as
follows:
Diameter of Siphon. │ Discharging Depth.
│
3 inches│ 13 inches
5 inches│ 23 inches
6 inches│ 30 inches
8 inches│ 35 inches
10 inches│ 60 inches
12 inches│ 72 inches
If the siphons installed are larger or smaller than those shown in these
tables, or if the particular make of siphon purchased has the same
diameter but a different discharging depth, proper allowance must be
made in proportioning the size of the dosing chamber.
In order to quickly convey the dose from the siphon chamber to the
filter beds at the rate at which the siphon discharges, the sewer from
the siphon chamber should be of proper size and should have a sufficient
gradient. For instance, with a 3–inch siphon the sewer should be 6
inches in diameter, with a gradient or fall of at least 12 inches per
100 feet; with a 5–inch siphon, the sewer should be 8 inches in
diameter, with a gradient of at least 6 inches in 100 feet; with a
6–inch siphon, the diameter of the sewer should be 8 inches, and should
have a gradient of at least 12 inches per 100 feet, or 10 inches with a
gradient of at least 3 inches per 100 feet; with an 8–inch siphon, 12
inches, with a gradient of at least 12 inches per 100 feet.
Public-domain text, read in full here on John Shaqi.