For such situations, a steam ejector connected to the suction pipe
near the pump is advised, and may be required in addition to the
regular priming pipes and tank. The size of the ejector should be
sufficient to exhaust the suction pipe within about three minutes.
Such ejectors will be considered as extras not included in the
ordinary pump fittings.
For cases where pump can only take its suction under a head, if
absolutely certain that the level of the suction water will never
fall below level of center of pump, these priming pipes may be
omitted, but openings for them into the pump shell must be provided
and capped or plugged.
_A foot valve on a fire-pump suction is not advised_ except in very
rare cases, as with a lift of 18 feet or a suction pipe 500 feet or
more long. A foot valve is not needed when there is a good efficient
set of priming arrangements as described above and it is commonly
found this gives a false sense of security, and that with a fire-pump
left standing several days the water will often be found to have
leaked back, so that it is no better than if no foot valve had been
used.
A foot valve must of necessity generally be located where it is
inaccessible for quick repairs, and as they grow old, foot valves
are often a source of trouble. Where a suction pipe is exposed even
slightly to frost, a foot valve is specially objectionable.
_A priming tank is provided for the purchaser_ in all cases where
there is ever to be any lift on the suction. It is generally advised
that this tank have a capacity of one-half of what the pump can throw
at full speed in a minute. This means 250 gallons for a 500-gallon
pump and 500 gallons for a 1,000-gallon pump, etc. It is the
intention to make the pump a truly “independent source” of supply,
therefore the need of a special priming tank.
OLDER PRIMING ARRANGEMENTS.
The form of priming arrangement heretofore used, with metal check
valves, one main 2-inch priming valve, and 1-inch priming pipes,
separate controllable air cocks, may be retained on all pumps at
present in service, and will be considered satisfactory, if kept in
good order.
If in any case such checks give trouble the priming arrangement may
be changed and valves like Fig. 14 or rubber checks as described
in sections _f-j_, made up in detachable form,[D] may be put on if
desired, where the connections on the pump permit them.
Where neither method is desired or where neither is feasible the faulty
checks may be replaced by a special type such as are now made for
this use, by the Locke Regulator Company, of Salem, Mass. These are
1-inch check valves, adapted to use a small disc of medium hard rubber,
similar to a pump valve.
These fittings are very near the dimensions of the commercial check
valve, so that with slight shortening of piping connections they will
fit into the present arrangements, and give satisfaction.
47. DRAIN COCKS.