Records of Steam Boiler ExplosionsMarten, Edward Bindon
History
Records of Steam Boiler Explosions
Marten, Edward Bindon
Steam-boiler explosions
If however the water were turned on again before the overheating had
gone so far, and the feed pipe were, as usual, carried down to nearly
the bottom of the boiler, the water would gradually creep up the heated
sides and cool the plates, the heat of which would not be sufficient
to cause greater evaporation than the ordinary safety valves would
carry off. The danger would not arise so much from the excess of steam
generated by the heat accumulated in the heated plates of the boiler,
as from the injury and strain that would be caused to the plates by
the undue expansion and sudden contraction, especially as this action
would take place on only a portion of the boiler. A singular case,
bearing on this point, may be mentioned. A four-furnace upright boiler,
like that shown in Fig. 44, happened to run so nearly empty, through
the accidental sticking of the self-acting feed apparatus, that the
level of the water sank to the top of the hemispherical end forming
the bottom of the boiler. The feed apparatus then became released of
itself, and, the feed being turned full on, the water gradually rose
until the whole occurrence was only discovered by the leaking at the
seams that had been sprung, which caused so much steam in the flues
as to stop the working of the furnaces. The overheating had been
sufficient to buckle the plates, and in one place a rupture had almost
commenced; but there was no explosion. By way of direct experiment upon
this point, boilers have been purposely made red-hot and then filled
with cold water, without causing explosion.
It has been supposed that boilers sometimes explode from overheating
without the water level being below the usual point, or without
the accumulation of scurf previously alluded to, but simply by the
rapidity of the evaporation from an intensely heated surface causing
such a continuous current of steam as to prevent the proper contact
of the water with the heated plate. Such has been the cause assigned
for the explosion of a three-furnace upright boiler at Birmingham in
1865, shown in Fig. 75. A piece of plate about 3 ft. by 1-1/2 ft. was
blown out of the side, at a place where an enormous flame impinged
continually. The plates had first bulged out, and then given way in the
centre of the bulge, each edge being doubled back and broken off. There
was no positive evidence as to the water supply; but the crown of the
centre tube, which was much above the bottom of the part blown out,
remained uninjured.