Many explosions have been caused by the want of proper apparatus for
enabling the attendant to tell the height of the water and the pressure
of the steam, and also by the want of sufficient apparatus for supply
of feed water and escape of steam, or by the failure of one or other
of these; but such explosions can only be referred to generally in
the present paper. The mountings on a boiler are usually so open to
observation, and the importance of having them good and efficient is
so universally acknowledged, that much remark is not needed. Mention
has already been made of the sticking of self-acting feed apparatus as
a cause of mischief, and similar failures of floats and gauges have
constantly happened; but this should by no means be considered to
condemn self-acting apparatus, either for assisting in the steadiness
of working, or for giving warning of danger. The apparatus however
should be relied on for assistance only; and an attendant cannot be
called careful who leaves a boiler dependent on such apparatus without
watching. The self-acting principle has been seen by the writer applied
in a novel and useful way in a recording pressure gauge, which proved
the more interesting as it had shown the actual pressure of steam
at the time of the explosion of one of the boilers with which it was
connected.
Among the numerous boiler explosions that have been attributed to
over-pressure through deficient arrangements for escape of steam, in
many cases the safety valves have been placed on the steam pipes in
such a manner that the communication with them was cut off whenever
the steam stop-valve was shut, which is just the time when the safety
valves are most wanted. Safety valves are too often found needlessly
overweighted; and it is believed that many boilers are constantly
worked with safety valves so imprudently arranged and weighted, that
they could not carry off all the steam the boilers would generate
without a very great increase of pressure.
* * * * *