From these considerations, with the siphon dose 20 gallons per person, it
is usually a safe rule to provide 50 feet of 3-inch tile for each person
served and to lay the lines 10 feet apart. Such provision gives a capacity
within the bore of the tile lines about equal to the siphon dose, and
as some sewage is wasted at each joint a reasonable factor of safety is
provided. A spacing of 10 feet will, it is believed, permanently prevent
the extension of lateral absorption from line to line, provided the area
is fairly well drained. As between 3-inch and 4-inch tile the smaller
size costs less and is better calculated to taper the dose to small
proportions. Four-inch tile is less likely to get out of alignment or to
become clogged; a length of 28 feet has the same capacity in the bore as
50 feet of 3-inch.
Good-quality drain tile in 1-foot lengths or second-quality sewer pipe
in 2-foot lengths may be used. The lines are generally laid in parallel
runs, but may be varied according to the topography. Layouts 1, 2, and 3,
figure 29, for flat or gently sloping land, run with the slope; layout 4,
for steep slopes, runs back and forth along the contour in a series of
long flat sweeps and short steep curves. The grade of the runs and sweeps
should be gentle, rarely more than 10 or 12 inches in 100 feet. In layouts
1, 2, and 3, figure 29 especially, it is desirable that the last 20 feet
of each run should be laid level or given a slight upward slope, thus
guarding against undue flow of sewage to the lowest ends of the system.
Fig. 29.--Methods of laying distribution system: Methods 1, 2, and 3 for
flat or gently sloping land; method 4 for steep slopes (see also fig. 32);
_A_, direction of slope; _B_, contour of field; _C_, sewer from tank,
preferably size 5 inch, though 4 or 6 inch may be used, depending on
the fall and the size of the siphon (see table, fig. 26); _D_, =V=-branch
set to divide the flow exactly; _E_, reducer, to 4 inches; F, 1/8 bend,
4-inch; _G_, increaser, from 4 inches; _H_, increaser, 3 to 4 inches; _I_,
reducer, 4 to 3 inches; _J_, distribution tile, 3-inch; _K_, distribution
tile, 4-inch.
The runs should be laid no deeper than necessary to give clearance when
plowing and prevent injury from frost. Ten inches of earth above the top
of the tile is sufficient generally throughout the southern half of the
United States and 18 inches generally in the North, but if the field
is exposed or lacks a thick heavy growth of grass the cover should be
increased to 2-1/2 or 3 feet near the Canadian line. What is better, the
tile in all instances may be laid with a 10-inch cover and in cold weather
the runs may be covered with hay, straw, or leaves weighted down, which
may be removed in the spring.
[Illustration: Fig. 30.--Four methods of protecting open joints in
distribution lines--an all-important work. Sketches show cross-section and
longitudinal views; the depth from the surface of the ground to the top of
the tile is about 10 inches.