The size and length of distribution tile and the spacing of the lines
or runs admit of considerable variation in different soils. Water sinks
rapidly in gravels and sands, and hence larger tile and shorter length are
permissible than in close soils. Lateral movement is slow in all soils,
but extends farther in gravels and sands than in close soils. In average
soils the effect on vegetation 5 feet away from the line is practically
nil.
From these considerations, with the siphon dose 20 gallons per person, it
is usually a safe rule to provide 50 feet of 3-inch tile for each person
served and to lay the lines 10 feet apart. Such provision gives a capacity
within the bore of the tile lines about equal to the siphon dose, and
as some sewage is wasted at each joint a reasonable factor of safety is
provided. A spacing of 10 feet will, it is believed, permanently prevent
the extension of lateral absorption from line to line, provided the area
is fairly well drained. As between 3-inch and 4-inch tile the smaller
size costs less and is better calculated to taper the dose to small
proportions. Four-inch tile is less likely to get out of alignment or to
become clogged; a length of 28 feet has the same capacity in the bore as
50 feet of 3-inch.
[Illustration: Fig. 27.--Methods of laying distribution system: Methods
1, 2, and 3 for flat or gently sloping land; method 4 for steep slopes
(see also fig. 30); _A_, direction of slope; _B_, contour of field; _C_,
sewer from tank, preferably size 5 inch, though 4 or 6 inch may be used,
depending on the fall and the size of the siphon (see table, fig. 24);
_D_, =V=-branch set to divide the flow exactly; _E_, reducer, to 4 inches;
_F_, 1/8 bend, 4-inch; _G_, increaser, from 4 inches; _H_, increaser, 3
to 4 inches; _I_, reducer, 4 to 3 inches; _J_, distribution tile, 3-inch;
_K_, distribution tile, 4-inch]
Good-quality drain tile in 1-foot lengths or second-quality sewer pipe
in 2-foot lengths may be used. The lines are generally laid in parallel
runs, but may be varied according to the topography. Layouts 1, 2, and 3,
Figure 27, for flat or gently sloping land, run with the slope; layout 4,
for steep slopes, runs back and forth along the contour in a series of
long flat sweeps and short steep curves. The grade of the runs and sweeps
should be gentle, rarely more than 10 or 12 inches in 100 feet. In layouts
1, 2, and 3, Figure 27 especially, it is desirable that the last 20 feet
of each run should be laid level or given a slight upward slope, thus
guarding against undue flow of sewage to the lowest ends of the system.