Sewerage and Sewage TreatmentBabbitt, Harold E. (Harold Eaton)
History
Sewerage and Sewage Treatment
Babbitt, Harold E. (Harold Eaton)
Sewage disposal; Sewerage
8. Cincinnati, O.; Residential, average.
9. Cincinnati, O.; Commercial, average.
10. Average of 7 cities.
The fluctuations of flow in commercial and industrial districts are so
different from those in residential districts that the formulas given
should not be used in the design of sewers other than those draining
residential areas. It is reasonable to suppose that fluctuations in
rates of flow from industrial districts are dependent upon the character
of the tributary industries. A study of these industries will give
valuable light on the maximum and minimum rates at which sewage will be
delivered to the sewers.
Hourly, daily, and seasonal fluctuations in rates of sewage flow are of
interest in the design of pumping stations to give knowledge of the
rates at which the pumps must operate at various periods. The
fluctuations in rates of sewage flow during various hours and days in
different cities and districts are shown in Fig. 10. Fluctuations in
rate of flow of sewage lag behind fluctuations in rate of water
consumption, the time being dependent on the distance through which the
wave of change must travel in the sewer.
=26. Effect of Ground Water.=—Sewers are seldom laid with water-tight
joints. Since they usually lie below the ground water level it is
inevitable that a certain amount of ground water will enter. Various
units have been suggested for the expression of the inflow of ground
water in an attempt to include all of the many factors. Some of these
units are: gallons per acre drained by the sewer per day, gallons per
mile of pipe per day, gallons per inch diameter per mile of pipe per
day, etc. Since the ground water enters pipe sewers at the joints, the
longer the joints the greater the probability of the entrance of ground
water. The last unit is therefore the most logical but the accuracy of
the result is scarcely worthy of such refinement and the unit usually
adopted is gallons per mile of pipe per day.
No definite figure can be given for the amount of ground water to be
expected in sewers since the character of the soil and the ground water
pressure must be considered. Relatively normal infiltration may be found
from 5,000 to 80,000 gallons per mile of pipe per day. The minimum is
seldom reached in wet ground and the maximum is frequently exceeded.
Table 12 shows the amount of ground water measured in various sewers as
given by Brooks.[21]