Fear has at times been expressed that certain waste gases, such as those
containing sulphur fumes, will have a deleterious action on the heating
surface of the boiler. This feature has been carefully watched, however,
and from plants in operation it would appear that in the absence of
water or steam leaks within the setting, there is no such harmful
action.
[Illustration: Fig. 32. Babcock & Wilcox Boiler Arranged for Utilizing
Waste Heat from Open Hearth Furnace. This Setting may be Modified to
Take Care of Practically any Kind of Waste Gas]
CHIMNEYS AND DRAFT
The height and diameter of a properly designed chimney depend upon the
amount of fuel to be burned, its nature, the design of the flue, with
its arrangement relative to the boiler or boilers, and the altitude of
the plant above sea level. There are so many factors involved that as
yet there has been produced no formula which is satisfactory in taking
them all into consideration, and the methods used for determining stack
sizes are largely empirical. In this chapter a method sufficiently
comprehensive and accurate to cover all practical cases will be
developed and illustrated.
Draft is the difference in pressure available for producing a flow of
the gases. If the gases within a stack be heated, each cubic foot will
expand, and the weight of the expanded gas per cubic foot will be less
than that of a cubic foot of the cold air outside the chimney.
Therefore, the unit pressure at the stack base due to the weight of the
column of heated gas will be less than that due to a column of cold air.
This difference in pressure, like the difference in head of water, will
cause a flow of the gases into the base of the stack. In its passage to
the stack the cold air must pass through the furnace or furnaces of the
boilers connected to it, and it in turn becomes heated. This newly
heated gas will also rise in the stack and the action will be
continuous.
The intensity of the draft, or difference in pressure, is usually
measured in inches of water. Assuming an atmospheric temperature of 62
degrees Fahrenheit and the temperature of the gases in the chimney as
500 degrees Fahrenheit, and, neglecting for the moment the difference in
density between the chimney gases and the air, the difference between
the weights of the external air and the internal flue gases per cubic
foot is .0347 pound, obtained as follows:
Weight of a cubic foot of air at 62 degrees Fahrenheit = .0761 pound
Weight of a cubic foot of air at 500 degrees Fahrenheit = .0414 pound
------------------------
Difference = .0347 pound