Another feature in stoker-fired plants is in the cleaning of fires. It
must be impressed upon the operatives that before the fires are cleaned
they should be put into condition for such cleaning. If this cleaning is
done at a definite time, regardless of whether the fires are in the best
condition for cleaning, there will be a great loss of good fuel with the
ashes.
3rd. It is necessary that in each individual plant there be a basis on
which to judge the cleanliness of a boiler. From the operative's
standpoint, it is probably more necessary that there be a thorough
understanding of the relation between scale and tube difficulties than
between scale and efficiency. It is, of course, impossible to keep
boilers absolutely free from scale at all times, but experience in each
individual plant determines the limit to which scale can be allowed to
form before tube difficulties will begin or a perceptible falling off in
efficiency will take place. With such a limit of scale formation fixed,
the operatives should be impressed with the danger of allowing it to be
exceeded.
4th. The operatives should be instructed as to the losses resulting from
excess air due to leaks in the setting and as to losses in efficiency
and capacity due to the by-passing of gases through the setting, that
is, not following the path of the baffles as originally installed. In
replacing tubes and in cleaning the heating surfaces, care must be taken
not to dislodge baffle brick or tile.
[Illustration: 2000 Horse-power Installation of Babcock & Wilcox
Boilers, Equipped with Babcock & Wilcox Chain Grate Stokers at the
Sunnyside Plant of the Pennsylvania Tunnel and Terminal Railroad Co.,
Long Island City, N. Y.]
5th. That an increase in the temperature of the feed reduces the amount
of work demanded from the boiler has been shown. The necessity of
keeping the feed temperature as high as the quantity of exhaust steam
will allow should be thoroughly understood. As an example of this, there
was a case brought to our attention where a large amount of exhaust
steam was wasted simply because the feed pump showed a tendency to leak
if the temperature of feed water was increased above 140 degrees. The
amount wasted was sufficient to increase the temperature to 180 degrees
but was not utilized simply because of the slight expense necessary to
overhaul the feed pump.
The highest return will be obtained when the speed of the feed pumps is
maintained reasonably constant for should the pumps run very slowly at
times, there may be a loss of the steam from other auxiliaries by
blowing off from the heaters.