Acetylene
(_a_) Calcium carbide in quantities not to exceed six hundred (600)
pounds may be stored, when contained in approved metal packages not to
exceed one hundred (100) pounds each, inside insured property, provided
that the place of storage be dry, waterproof and well ventilated, and
also provided that all but one of the packages in any one building shall
be sealed and the seals shall not be broken so long as there is carbide
in excess of one (1) pound in any other unsealed package in the building.
(_b_) Calcium carbide in quantities in excess of six hundred (600)
pounds must be stored above ground in detached buildings, used
exclusively for the storage of calcium carbide, in approved metal
packages, and such buildings shall be constructed to be dry, waterproof
and well ventilated.
(_c_) Packages to be approved must be made of metal of sufficient
strength to insure handling the package without rupture, and be provided
with a screwed top or its equivalent.
They must be constructed so as to be water- and air-tight without the use
of solder, and conspicuously marked "CALCIUM CARBIDE--DANGEROUS IF NOT
KEPT DRY."
The following is a summary of the AUSTRIAN GOVERNMENT rules relating to
the storage and handling of carbide:
(1) It must be sold and stored only in closed water-tight vessels, which,
if the contents exceed 10 kilos., must be marked in plain letters
"CALCIUM CARBIDE--TO BE KEPT CLOSED AND DRY." They must not be of copper
and if soldered must be opened by mechanical means and not by
unsoldering. They must be stored out of the reach of water.
(2) Quantities not exceeding 300 kilos. may be stored in occupied houses,
provided the single drums do not exceed 100 kilos. nominal capacity. The
storage-place must be dry and not underground.
(3) The limits specified in Rule 2 apply also to generator-rooms, with
the proviso also that in general the amount stored shall not exceed five
days' consumption.
(4) Quantities ranging from 300 to 1000 kilos. must be stored in special
well-ventilated uninhabited non-basement rooms in which lights and
smoking are not allowed.
(5) Quantities exceeding 1000 kilos. must be stored in isolated fireproof
magazines with light water-tight roofs. The floors must be at least 8
inches above ground-level.
(6) Carbide in water-tight drums may be stored in the open in a fenced
enclosure at least 30 feet from buildings, adjoining property, or
inflammable materials. The drums must be protected from wet by a light
roof.
(7) The breaking of carbide must be done by men provided with respirators
and goggles, and care taken to avoid the formation of dust.
(8) Local or other authorities will issue from time to time special
regulations in regard to carbide trade premises.