Diameter of │Cubic Contents of│ Amount of Water │Area of Pipe 1728
Circular Pipe or │ Gas in each 100 │to produce 1 inch│ = 1 cubic foot.
Drain. │ feet length of │rise of Liquid in│
│ Drain Pipe or │ Detector. │
│ Sewer. │ │
─────────────────┼─────────────────┼─────────────────┼─────────────────
ins. │ cub. ft. │gals. pts. ozs. │
4│ 8–1255/1728│ 0 1 7│ 12·566
6│ 19–1096/1728│ 0 4 0│ 28·274
9│ 44–308/1728│ 1 1 2│ 63·617
12│ 78–932/1728│ 2 0 5│ 113·097
15│ 122–1242/1728│ 3 1 6│ 176·715
18│ 176–1234/1728│ 4 5 0│ 254·469
19│ 196–1546/1728│ 5 1 1│ 283·529
20│ 218–288/1728│ 5 5 7│ 314·160
21│ 240–913/1728│ 6 2 1│ 346·361
22│ 263–1695/1728│ 6 7 0│ 380·133
23│ 288–917/1728│ 7 4 2│ 415·476
24│ 314–276/1728│ 8 1 6│ 452·390
25│ 340–1530/1728│ 8 7 0│ 490·875
26│ 368–1212/1728│ 9 4 13│ 530·930
27│ 397–1063/1728│ 10 2 14│ 572·556
28│ 427–1147/1728│ 11 1 12│ 615·753
29│ 458–1201/1728│ 11 7 8│ 660·521
30│ 490–1512/1728│ 12 6 9│ 706·860
─────────────────┴─────────────────┴─────────────────┴─────────────────
The method of testing drains and fittings by compression of gas is as
follows:—When the drainage plan of a building exists, the work of
testing by compression of gas in the drain will be a very simple matter.
Plate 1 shows the drains as laid to a semidetached villa, with two
inlets from sinks marked 1, one from bath overflow marked 2, and two
from the soil-pipes of closets in the basement and first-floor marked 3.
The drain from A to B is a 6-inch stoneware pipe, and its length is 100
feet. The amount of gas in it would be 19–1096/1728 cubic feet. The
branch drains from the other inlets are 4 inches in diameter, and the
collected lengths are 50 feet, and the quantity of gas in them would be
4–627/1728 cubic feet, giving a total in the whole of the drain of
nearly 24 cubic feet.