M M′ are the flow and return mains, the dynamos bridging them across at
one end. If the mains were very long, those near to the dynamos would
be exhausting the supply, and the lamps at the remote end would not get
the full pressure. A system of feeders has been devised so that each
lamp, no matter where it may be, shall have approximately the full 110
volts working through it. Fig. 17 shows a long circuit consisting of
two branch mains bridged by a large number of lamps, _l l_, and D D are
the dynamos at the central-station. Series of feeders, _f f′_, have to
be taken from the dynamo mains and fed direct into the branch mains
at various points, _d d′_, _b b′_, _c c′_, in order to distribute the
electrical pressure equally.
THE THREE-WIRE SYSTEM.
The ordinary parallel system is undoubtedly suitable for small
installations; but when the area to be lighted is extensive, it is
impossible to proportion the mains, with a view to economy in the cost
of copper, without sacrificing energy wasted in heating the conductors.
In Figs. 16, 17, the lamps are shown in simple parallel; but if two
dynamos are connected together, and a main wire is run from each of
their two extreme terminals and a third wire from the branch connecting
the two machines, we have what is known as the three-wire system,
which was invented by Edison in America, and Hopkinson in England,
almost simultaneously. Although by using the third wire there is a
saving in copper over the parallel plan, the maximum gain is not more
than 25 per cent., under the best conditions; when the district to be
illuminated is not more than 400 to 600 yards from the central-station,
the three-wire system answers well, but as soon as this distance is
exceeded the cost of the mains begins to mount up at a most alarming
rate. Although there are many Edison installations in the United States
on this system and a few on the Continent, it has only been used here
in a few instances for factory lighting.
THE EDISON SYSTEM AT MILAN.