Electric light plants -- Europe
far the largest amount of current is drawn off for the lighting of the
Scala Theatre, the stage-lighting alone taking more than one thousand
lights: if these were all turned on suddenly, the other lights in the
district would be dimmed; to obviate this, auxiliary feeders have been
run, which are used only when any great increase is expected;
commutators similar to those referred to above also regulate these
feeders without any special attention. The pressure at any point in the
system is by this means easily controlled, and affords an illustration
of what is perhaps not the most economical, but is found to be the most
practicable, way of maintaining a constant potential in a district
where the amount of output of current is suddenly doubled. Fig. 18 is a
plan of the network system of conductors laid through a large portion
of the city; the conductors are in outward appearance similar to
gas-pipes, the current passing through semicircular bars of copper,
embedded both for the flow and return in the same iron tube, which is
laid underground in a shallow trench. The house-supply is drawn from
the mains, and these are connected to the feeders by means of ordinary
junction-boxes, which each contain a fusible cut-out. The bridge-boxes
allow of expansion of the line, and have connections for testing
purposes. The insulation is extremely good, mainly on account of the
favourable nature of the ground, which is chiefly gravel; no trouble
has been experienced with leakage, nor has the service ever been
interrupted. The cut-outs are of an improved Edison form, but have the
disadvantage attending all lead plugs where the current is great, in
that, to guard against accidental melting due to the heating effect of
the current, the sectional area of the lead has to be much larger than
would be otherwise necessary. In fact, these cut-outs will protect the
cable against a bad short circuit, but nothing else.