Having closed the switch, if the motor fail to start, it will be advisable
to remove the load if possible, as the failure may arise from an overload
of the machine. This being effected and the motor not starting, the
terminals of the latter should be tested by the means already described
for voltage. If no voltage be generated, a broken circuit or a defective
contact may be looked for in the main fuse, switch, or starting box. The
resistance coils of the latter, through the heat developed, frequently
break in positions out of sight. If a defective contact of this nature
cannot readily be seen, the contact arm should be moved slowly over the
contacts, as it is possible the broken coil may be cut out of circuit by
this means.
[Illustration: Figs. 744 to 746.--Cutler-Hammer motor starting rheostats
with no voltage and overload release. Fig. 744, starter with fixed button
contact, fig. 745, with renewable button contact, and fig. 746, with
contact segments. In construction the resistance is enclosed in a pressed
steel box on which is mounted a marbleized slate panel carrying the
starting lever, contacts and protective devices. By means of a calibrated
scale, the overload release (shown in the lower left hand corner, figs.
744 and 745, and in the lower right hand corner fig. 746) can be set
to break the circuit on any overload not exceeding 50 per cent. of the
rated capacity of the motor. This calibrated scale can also be used for
determining, with a fair degree of accuracy, the amount of current being
consumed by the motor.]
If a difference of pressure exist between the motor terminals, the
field magnets will, if shunt or compound wound and in good order,
be excited, which may be ascertained by means of a bar of iron. If
no magnetism be present, it will of course, indicate a broken or
bad connection, either between the terminals of the field coils, or
one or more of the coils themselves. If the bar pull strongly, the
position of the brushes upon the commutator in regard to the neutral
points should be ascertained, and the rocker adjusted, if necessary,
to bring them into their correct positions. If this fail to start the
motor, the connecting leads from the motor terminals to the brushes
and the brushes themselves should be carefully examined for broken
or bad connections, and defective contact of the brushes with the
commutator. In the latter case, it may arise from a dirty state of
the commutator, or from the brushes not being fed properly. If due
to these causes, pressing the brushes down upon the commutator with
the fingers will probably start the motor. If the failure to start
arise from none of these causes, it is probably due to the field coils
acting in opposition, or to a short circuited armature. This latter
remark applies more especially to motors provided with drum armatures.