Lightning Conductors: Their History, Nature, and Mode of ApplicationAnderson, Richard, F.C.S.
History
Lightning Conductors: Their History, Nature, and Mode of Application
Anderson, Richard, F.C.S.
Lightning conductors
‘It is therefore not necessary to connect large masses of metal, such
as engines, tanks, &c., to the walls, if they are entirely within the
building. If, however, any conductor, such as a telegraph-wire, or a
metallic supply-pipe for water or gas, comes into the building from
without, the potential of this conductor may be different from that
of the building, unless it is connected with the conducting shell of
the building. Hence the water or gas supply-pipes, if any enter the
building, must be connected to the system of lightning conductors; and
since to connect a telegraph-wire with the conductor would render the
telegraph useless, no telegraph from without should be allowed to enter
a powder-mill, though there may be electric bells and other telegraphic
apparatus within the building. I have supposed the powder-mill to
be entirely sheathed in thick sheet copper. This, however, is by no
means necessary in order to prevent any sensible electrical effect
taking place within it, supposing it struck by lightning. It is quite
sufficient to enclose the building with a network of a good conducting
substance. For instance, if a copper wire, say No. 4, B. W. G. (0·238
inch diameter) were carried round the foundation of the house, up each
of the corners and gables, and along the ridges, this would probably
be a sufficient protection for an ordinary building against any
thunderstorm in this climate. The copper wire may be built into the
wall to prevent theft, but should be connected to any outside metal,
such as lead or zinc on the roof, and to metal rain-water pipes. In the
case of a powder-mill, it might be advisable to make the network closer
by carrying one or two additional wires over the roof and down the
walls to the wire of the foundation. If there are water or gas-pipes
which enter the building from without, these must be connected with
the system of conducting wires; but if there are no such metallic
connections with distant points, it is not necessary to take any pains
to facilitate the escape of the electricity into the earth; still less
is it advisable to erect a tall conductor with a sharp point in order
to relieve the thunder-clouds of their charge.
[Illustration: Fig. 38. ARRANGEMENT OF PROFESSOR CLERK MAXWELL’S
LIGHTNING CONDUCTORS.]
‘It is hardly necessary to add, that it is not advisable, during a
thunderstorm, to stand on the roof of a house so protected, or to stand
on the ground outside, and lean against the wall.’