The corrosion most to be dreaded, because most difficult to detect, is
that which takes place where the boiler is in contact with brickwork;
and it is found alike in all forms of boilers set in brickwork. When
found at the part where the side flues are gathered in at the top
against the boiler, it is usually occasioned by the leaking of fittings
or feed pipes, or by rain being allowed to run between the boiler and
the brickwork. More than one explosion has been caused by the droppings
from a roof being allowed to fall upon the tops of the flues. When the
corrosion is found at the point where the bottom flue walls touch the
boiler, it is frequently caused by the leaking of seams that have been
strained by the weight of the boiler; and this often arises from want
of care to replace the brickwork, after repair of the boiler or flues,
in such a position as to take again its proper proportion of the weight
of the boiler. Cases have been met with where the shape of the bottom
of large boilers has been quite altered by such means. The brackets
on the sides of heavy boilers have not only been strained so that the
rivets or bolts have leaked and caused corrosion, but they have also
bent or cracked the side plates of the boiler. The bracket shown at B
in Fig. 53, page 40, made of only an angle iron with a piece of plate
attached, is especially liable to cause injury if the brickwork is not
rebuilt close up to the angle iron, as the leverage is so great. This
is avoided by the better form of bracket shown at C, consisting of an
elbow of flat bar-iron rivetted at top and bottom to the boiler.
[Illustration: _Fig. 68._]